VELTRON II
Air Monitor Corporation
116-011-98.P65 (8/30/10)
VELTRON II - IO&M Manual
25
5.8 – TRANSMITTER SCALING & CONFIGURATION
(con't)
SECTION 5 – OPERATION
Reset Default Values
NO
Calculate Diff. Pres
XXXXX in.WC
Calculate Flow
XXXXX CFM
Pitot Tube Coefic.
1.00
Dry Molecular Weight
28.966 Lb/Lb-Mole
0.01 to 1.00
in 0.01 increments
0.000 to 65.000
Lb/Lb-Mole
in 0.001 increments
Return to
MAIN MENU
Dry Molecular Weight
Selection
Pitot Tube Coefic.
Selection
Calculate Flow
Value
5
Calculate Diff. Pres
Value
7
Update Flow
Value
5
Update Operating Span
Diff. Press. Value
7
Reset Calculation
Default Values
EXIT
Update Flow
NO
Update Operating Span
NO
NO or YES
4
Calculator uses parameters entered in Process Configuration (ie.Type,
Max., Area, Units, etc.) as necessary to perform calculation.
Steps in this Section marked with * indicate values or choices
previously made in Process Congiuration.
Exits to Trans.
Scaling &
Configuration Menu
Percentage Water
0.00%
Wet / Dry Flow Basis
DRY
0.00 to 50.00%
in 0.01 increments
DRY or WET
Wet / Dry Flow Basis
Selection
*
Percentage Water
Selection
*
6 Depends on selection immediately above.
5 Available only with Calculate Flow.
7
Available only with Calculate D.P.
NO or YES
NO or YES
Continued from next page