MASS-tron II/CEM
Air Monitor Corporation
116-004-94.P65 (8-31-10)
MASS-tron II/CEM
- IO&M Manual
2
2.3 – INPUTS/OUTPUTS
Analog Input
. Analog input for temperature is available
and field configurable via jumper for 0-5VDC, 0-10VDC, or
4-20mADC.
Analog Outputs
. Transmitter/AUTO-cal Reporting,
Temperature, Absolute Pressure, and one selectable
output are individually configurable via jumper for 0-5VDC,
0-10VDC, or 4-20mADC.
Digital Inputs
. Dry contacts input from "smart" relay for
AUTO-purge start signal and AUTO-cal external start.
Digital Outputs
. Dry contacts for optional Alarm or AUTO-
purge activation/acknowledgment. Contacts are rated for:
Maximum 3 amps @ 24 to 120VAC
Maximum 3 amps @ 24VDC
Maximum 0.5 amps @ 48VDC
Temperature Compensation Selection
. Push-button
selection of linearized or non-linear input. Choice of
thermocouple or 100 ohm platinum RTD temperature
sensor type.
Type E
-50 to 1750ºF
-50 to 950ºC
Type T
-50 to 750ºF
-50 to 400ºC
Type J
-50 to 2000ºF
-50 to 1090ºC
Type K
-50 to 2000ºF
-50 to 1090ºC
RTD
-50 to 1500ºF
-50 to 815ºC
Pressure Compensation
. Absolute pressure
(atmospheric or duct static), up to 60 IN Hg.
Network Communication
. Optional ModBus TCP/IP
over Ethernet.
2.4 – POWER
Power Supply
. 24VDC (20-40VDC) or 24VAC (20-28VAC).
Power Consumption
. 18VA @ 24VAC, 13VA @ 24VDC.
Circuit Protection
. Power input is isolated, fused, and
reverse polarity protected.
2.1 – TRANSMITTER
Ranges
. Natural Full Spans
0 to 25.00 IN w.c.
0 to 10.00 IN w.c.
0 to 5.00 IN w.c.
0 to 2.00 IN w.c.
0 to 1.00 IN w.c.
Span Rangeability
. The calibrated span can be down
ranged to 40% of the Natural Span.
Accuracy
. ±0.1% of Natural Span, including non-
linearity, hysteresis, and non-repeatability.
Stability
. ±0.5% of Natural Span for six months.
Transducer Response Time
. 0.5 second to reach
98% of a step change.
Temperature Effect
. Zero. None; corrected by AUTO-
zero. Span. 0.015% of Full Span/ºF.
Mounting Position Effect
. None; corrected by AUTO-
zero.
Span and Zero Adjustment
. Digital, via internally
located push-buttons.
Automatic Zeroing
. Accuracy. Within 0.1% of
calibrated span. Frequency. Every 1 to 24 hours
selectable on 1 hour intervals.
Low Pass Filtration
. Response time to reach 98% of a
step change is adjustable from 2.0 to 256.0 seconds.
Overpressure and Static Pressure Limit
. 25 psig.
Temperature Limits
. –20 to 180ºF Storage.
+40 to 140ºF Operating.
Humidity Limits
. 0-95% RH, non-condensing.
2.2 – INDICATION
Displays
. Graphical backlit LCD provides up to five lines
of data display.
LED's indicate CPU Activated, AUTO-zero in Progress,
AUTO-zero over-ranged, AUTO-purge in Progress, and
AUTO-cal in Progress.
SECTION 2 – PERFORMANCE SPECIFICATIONS
2 – PERFORMANCE SPECIFICATIONS
0 to 0.50 IN w.c.
0 to 0.25 IN w.c.
0 to 0.10 IN w.c.
0 to 0.05 IN w.c.
24VAC
24VDC
120VAC
14.4VA
9.6W
19.2VA
14VA
9.0W
18.67VA
85VA
37W
106VA
73VA
37W
92VA
Standard
w/AUTO-purge
In Rush Contin In Rush Contin