MASS-tron II/CEM
Air Monitor Corporation
116-004-94.P65 (8-31-10)
MASS-tron II/CEM
- IO&M Manual
SECTION 5 – OPERATION
5.13 – ALARM CONFIGURATION
User can turn Alarm function ON or OFF, and set the following values:
Low Setpoint
:
Selected value of transmitter span, below which an alarm condition will exist. Value is selected in
same units as transmitter format.
Alarm Deadband
: Value that transmitter signal has to reach above before an activated alarm will reset. Value is
selected in same units as transmitter format.
Alarm Delay
:
Time between an alarm condition existing and alarm activation. Adjustable between 0.0 and 10.0
minutes in 0.1 minute increments.
37
- Alarm 1 Off / On Selection
- Alarm 1, Low Setpt Selection
- Alarm 1 Dead Band Selection
- Alarm 1 Delay Selection
- Return to MAIN MENU
Alarm 1 Off / On
OFF
Alarm1, Low Setpt
250
[units]
Alarm 1 Dead Band
0
[units]
Alarm 1 Delay
5.0 Min.
- Auto-Cal Configuration
Alarm Configuration
- Controller not installed
Alarm Configuration
Default selection shown.
Available selections:
OFF or ON
Depends on
Process
Type and Format
D
epends on
Process
Type and
Format
0.0 to 10.0 Min.
in 0.1increments
Return to
MAIN MENU
Operator Setup Main Menu