MASS-tron II/CEM
Air Monitor Corporation
116-004-94.P65 (8-31-10)
MASS-tron II/CEM
- IO&M Manual
6.5 – AUTO-span PRESSURE REFERENCE CALIBRATION
1. Disconnect tubing at output of AUTO-span Pressure Reference.
2. Connect manometer to output of AUTO-span Pressure Reference (see Figure 6.4).
3. Using coarse adjustment, adjust pressure as read on gauge to 9.0 ± 1.0 psi (tap gauge to eliminate any hysteresis).
4. Using reference adjustment, adjust reference pressure as read on manometer to desired percentage of full scale
input pressure (see Factory Set-Up Information Sheet).
5. Remove manometer and reconnect tubing removed in Step 1 above.
Figure 6.4
59
SECTION 6 – CALIBRATION