MASS-tron II/CEM
Air Monitor Corporation
116-004-94.P65 (8-31-10)
MASS-tron II/CEM
- IO&M Manual
31
SECTION 5 – OPERATION
5.8 – TRANSMITTER SCALING & CONFIGURATION (con't)
As an example of how to utilize the calculator, the following shows how to change the Operating Span if the process
temperature is 150ºF.
23. While in Transmitter Scaling & Configuration menu, use
UP
or
DN
to scroll to: Calculator for Max
Diff. Pres. or Flow
24. Press
ENT
to enter the Calculator for Max Diff. Pres. or Flow sub-menu.
Calculate D.P./Flow
Display will indicate:
Selection
25. Press
ENT
and display will indicate:
Calculate D.P./Flow
DIFF. PRES.
26. Press
ENT
and then
UP
twice and display will indicate:
Process Temperature
Selection
27. Press
ENT
and use
UP
button until temperature reads 150ºF.
28. Press
ENT
and scroll to:
Calculate Diff. Pres
Value
29. Press
ENT
and a new value for Differential Pressure will be displayed.
30. Press
ENT
and then
UP
and display will read:
Update Operating Span
Diff. Pres. Value
31. Press
ENT
, scroll to YES and press
ENT
, display will return to that shown in Step 30, and new operating span
will be stored in memory.
Note: If during this step, display indicated CAL. SPAN NOT UPDATED NAT. SPAN TOO LOW or HIGH, new
span is less than 40% or greater than 100% of the natural span of the transducer installed. User should
contact Factory for further assistance (see section 10.0).
32. To return to the Transmitter Scaling & Configuration menu, select EXIT in the Calculator for Max Diff. Pres. or
Flow sub-menu and press
ENT
.
33. To return to the Main Menu, select Return to MAIN MENU in the Transmitter Scaling & Configuration menu
and press
ENT
.