MASS-tron II/CEM
- IO&M Manual
29
5.8 – TRANSMITTER SCALING & CONFIGURATION
(con't)
User should not need to use the following Calculator unless:
a. Process parameters have changed and new Differential Pressure or Flow values are needed.
b. Mid-point operating Differential Pressure or Flow values are wanted.
c. It is desired to implement a single-point density compensation for process temperature and/or absolute pressure
that is significantly different than standard conditions (68ºF and 29.92" Hg).
Values entered in this section will have no effect on normal operation unless user enters YES in the Update Flow/
Operating Span Value menu item (see below).
SECTION 5 – OPERATION
Calculate D.P. / Flow
DIFF. PRES
.
DIFF. PRES.
or
FLOW
Calculate D.P. / Flow
Selection
Diff. Pressure
1.000 in. WC
0.000 to 25.000 inWC
in 0.001 increments
Diff. Pressure
Selection
13
Default selection shown.
Available selections:
Process Static Pres.
0.0 in.WC
14
Process Temp.
68°F
*
Standard Temp.
68°F
*
-295.0 to 1,630.0 in.WC
in 0.01 increments
-50 to 2000°F
in 1° increments
0 to 100ºF
in 1º increments
Calculator For Max Diff. Pres. or Flow
12
Standard Temp.
Selection
Process Temp.
Selection
Process Static Pres.
Selection
Bar.Pres or Elevat'n
BAROMETRICPRESSURE
BAROMETRCPRESSURE
or ELEVATION
Elevation
0 Feet
*
0 to 10,000 Feet or
0 to 3,048 Meters
Bar.Pres or Elevat'n
Selection
Barometric Pressure
29.92 in.Hg
*
20.00 to 32.00 in.Hg
in 0.01 increments
Barometric Pressure
Selection
14
Elevation
Selection
14
Static Pressur Units
in.WC
in WC, in.Hg, psig, Pa,
kPa, bars, mbars,
mm WC, mmHg, kg/m2
Static Pressur Units
Selection
Continued on next page