SECTION 5 – OPERATION
50
5.25 – MENU INACTIVITY TIMEOUT SELECTION
Allows user to select a time (minutes) after which the unit returns to Normal operation if no activity in the Operator
Menu.
1. While in Main Menu, use
UP
or
DN
to scroll to:
Menu Inactivity
Timeout Selection
2. Press
ENT
and display will indicate current timeout value (1 to 30 minutes or OFF).
3. Use
UP
or
DN
to change timeout value. Once desired value is displayed, press
ENT
. New setting will be stored
in memory and display will return to Main Menu.
Note: If user desires not to change the setting and return to Main Menu, press
ESC
. Unit will remain
programmed as it was originally.
-
Network Selection.
Menu Inactivity Timeout Select
-
Exit Operator Setup
M e nu Inactivity
10 M inute s
OFF or
1 to 30 minutes
in 1 minute increments
Default selection shown.
Available selections:
Ope rator Se tup M ain M enu