MASS-tron II/CEM
Air Monitor Corporation
116-004-94.P65 (8-31-10)
MASS-tron II/CEM
- IO&M Manual
5.16 – K-FACTOR CONFIGURATION
Caution
In the majority of applications, the use of a K-Factor is neither required nor desirable.
Before using the K-Factor feature, contact the Service Department (see Section 10) to review
the application and obtain assistance in determining the K-Factor gain and bias values.
User can turn K-Factor function ON or OFF, calculate a K-Factor gain and bias based on measured data, or select a K-
Factor gain value and K-Factor bias value. The K-Factor gain is a number applied as a multiplier to the differential
pressure and the K-Factor bias is an offset added to the differential pressure. Note: If K-Factor is ON, Process
displays will have an asterisk (*) after the description (i.e. FLOW*).
SECTION 5 – OPERATION
39
- Special Function Config
K - Factor Configuration
1
- Display Configuration
Default selection shown.
Available selections:
- K - Factor Off/On Selection
- K - Factor Type Selection
- Calculate K-Factor? Selection
2
- Numbr of Data Points Selection
3
- Measured Point 1 (2,3) Selection
3
- Reference Point 1 (2,3) Selection
3
- Perform Calculation
3
- Coefficient A (B,C,D,E,F,G) Selection
4
- K - Factor Exponent Selection
5
- K - Factor Gain Selection
5
- K - Factor Bias Selection
5
- Display Max D.P.
2
- Return to MAIN MENU
K- Factor Exponent
X.XXXX
0.500 to 2.000
0.0001 increments
K- Factor Configuration
Return to
MAIN MENU
K- Factor Off/On
OFF
OFF or ON
1 Not available if Process Type is D.P.
(see Transmitter Scaling & Config.)
3
Available only if YES is selected in Calculate
K-Factor?
Calculate K-Factor?
NO
NO or YES
Numbr of Data Points
One Pair
One Pair
Two Pair
Three Pair
Measured Point 1(2,3)
1,000 CFM
Uses Process Units
& Format Selected
in Process Config.
Reference Point 1(2,3)
1,000 CFM
Uses Process Units
& Format Selected
in Process Config.
5
Available only if NO is selected in Calculate
K-Factor? and depends on Type of K-Factor.
K-Factor Gain
X.XXX
K-Factor Bias
X.XX%
0.300 to 5.000 *
0.001 increments
-25.00 to25.00% or
in 0.01 increments
*Available range depends
on operating span versus
natural span.
Operator Setup Main Menu
K
- Factor Type
ST LINE BEFORE SQ RT
ST LINE BEFORE SQ RT
ST LINE AFTER SQ RT
POLYNOM AFTER SQ RT
PWR CURV AFTER SQ RT
2
Not available if K-Factor Type is Polynomial.
GAIN: 1.000
BAIS: 0.00%
GAIN: 1.000
EXPO: 1.0000
For
ST LINE BEFORE or
AFTER SQ RT
For
POWER CURVE AFTER
SQ RT
Coef A: +0.00
Allows selection of Coef
A, B,C,D,E,F,G
4
Available only if K-Factor Type is Polynomial.
Max. Diff. Pressure
X.XXXXX in. WC
Value based
calculated or
selected Gain / Bias