7 – MAINTENANCE
SECTION 7 – MAINTENANCE
The MASS-tron II/CEM is a solid state device having few mechanical parts requiring special periodic maintenance. The
following maintenance steps are not requirements, but guidelines for establishing a maintenance program for your
specific installation.
Operating experience should be used to set frequency of specific types of maintenance.
7.1 – CLEANLINESS
– Periodically inspect MASS-tron II/CEM for build-up of dust and debris.
– Keep field wiring terminal strips clean to preclude shorting between terminals.
– Verify condensation (or other sources of liquids) are not present inside the MASS-tron II/CEM.
7.2 – MECHANICAL
– Verify pressure signal connections are secure.
– Inspect pressure signal lines for any cracks or leaks.
– Verify mounting hardware is secure.
7.3 – ELECTRICAL
– Periodically inspect all wiring to the MASS-tron II/CEM for good connections and absence of corrosion.
7.4 – CALIBRATION
– MASS-tron II/CEM should have calibration verified annually as a minimum.