Page
101
of
125
√
√
√
√
The “Set Date/Time” assignment will set the date and time of the controller. The width can be set from 1
to 32 bits but should always be set to 32 to get the correct results. The input value will be read as the
number of seconds since 00:00:00 January 1, 1970 (POSIX time or Epoch time). If the input value
changes and it is non-zero the date and time of the controller will be set to the new value.
Set Date/Time (word swap)
Supported Feature
Bus Element
Bit
0-31
Polarity
N.O./N.C. Width Offset
√
√
√
√
The “Set Date/Time (word swap)” assignment is the same as the “Set Date/Time” assignment except the
high and low words (16bit) are swapped prior to evaluation. This is to correct the mixed endianness of
some PLC. See the “Set Date/Time” for behavior.
Verify PSet
Supported Feature
Bus Element
Bit
0-31
Polarity
N.O./N.C. Width Offset
√
√
√
√
√
The “Verify PSET” input will compare the current parameter set to the input value. Uses the width
parameter limit the width of the input bits read. The minimum width is 1 and the maximum is 8. After the
input is read the offset parameter will be added to the value do get the actual parameter set number.
If the parameter set input value does not match the current parameter of the controller the tool will be
disabled.
Clear Results
Supported Feature
Bus Element
Bit
0-31
Polarity
N.O./N.C. Width Offset
√
√
√
√
The “Clear Results” assignment will clear the latest results outputs (Ok, Nok, etc.) on the same bus.
Log Change
Supported Feature
Bus Element
Bit
0-31
Polarity
N.O./N.C. Width Offset
√
√
√
√
The “Log Change” assignment will add entries to the controller event log when the input changes.
Decrement Batch
Supported Feature
Bus Element
Bit
0-31
Polarity
N.O./N.C. Width Offset
√
√
√
√
The “Decrement Batch” assignment will remove the latest OK rundown from the current running JOB.
This will cause the JOB count to be reduced by one.
Increment Batch
Supported Feature
Bus Element
Bit
Polarity
Width Offset