129
107110-01 - 6/16
i.
Unplug the ignition, ground, and flame rod wires
from the ignition electrode and the flame rod (Figure 13.2).
j.
Use a 10 mm wrench to remove the four nuts
securing the fire door to the heat exchanger (Figure 13.2). Carefully
remove the door/blower/gas valve assembly from the heat exchanger, being careful not to damage the refractory
insulation on the inside of the door (see Refractory Warning on next page) or the electrodes.
k.
Inspect the heat exchanger combustion chamber and vacuum
any debris found on the coil surfaces. If necessary,
the coils may be brushed with a nonabrasive, nonmetallic brush. Do not use cleaning agents, solvents, acid or alkali
products of any type to clean the heat exchanger .
l.
Inspect the target wall and fire door insulation
. If either shows signs of damage, it must be replaced.
m.
Inspect the burner for heat damage
or other deterioration. Use a non-metallic brush or source of compressed air
to clean off dust or debris from ports.
n.
Inspect the ignition electrode and flame rod
for deposits. Clean any found with steel wool. Do not use sand paper
or Emory cloth for this cleaning. Inspect the ceramic portion of both of these parts for cracks and replace if any are
found. Verify that the ignition electrode gap is within the range shown in Figure 13.3.
o.
Inspect the blower gas valve assembly
, looking for dust, lint, or other debris that may have been drawn into this
assembly. Excessive deposits may be vacuumed out.
The blower/gas valve assembly used on the 150 MBH and 180 MBH may be disassembled to expose the“swirl
plate” (see Parts Section for identification of parts in this assembly). If it is necessary to clean the swirl plate,
carefully note the orientation of all parts during disassembly and use care not to damage the swirl plate vanes.
The venturi assembly used on the 80, 100, and 120 cannot be removed from the blower.
Inspect all rubber and plastic components on the blower/gas valve assembly, looking for deterioration. Replace
blower and/or gas valve if deterioration is found.
p.
Inspect and clean the condensate trap
. Place a bucket under the condensate cleanout cap on the bottom of the
boiler (see Figure 2.1) to catch water in the trap as well as the ball and ball support. Unscrew the cap, being careful
not to lose the ball or ball support. Flush any debris found in the trap with water – do not use other cleaning agents.
Reassemble the trap as shown in Figure 13.4.
q.
Reinstall the fire door/blower/gas valve assembly
, following the above steps in reverse order.
r.
Inspect the vent system to verify that
:
• All gaskets and joints between the boiler heat exchanger and terminal are leak tight.
• All supports are intact and vent system is properly pitched
• All pipe is in good condition. Look for damage such as cracks, heat distortion, discoloration, and embrittlement.
If any such damage is found, the pipe must be replaced and the cause of the damage identified.
• Vent/Intake terminals are in good condition, free from blockages, and still correctly located relative to doors,
windows,
decks,
etc.
• There is no gasoline, flammable liquids/vapors, or halogen based products stored in the vicinity of the
vent or inlet terminals. Also verify that there are no chemical products containing chlorine, chloride based salts,
chlorofluorocarbons, paint removers, cleaning solvents, or detergents stored near the air intake terminal.
Warning
Asphyxiation Hazard. Do not operate the boiler without the ball and ball support in place. Doing so could
result in flue gas leakage into the indoors resulting in personal injury or death from Carbon Monoxide (CO)
poisoning.
nOTiCE
attempting to clean the heat exchanger or trap with anything other than water could result in condensate
backup, causing the boiler to shut-down.
CaUTiOn
Do not over tighten fire door mounting nuts. Doing so could break the fire door mounting studs. If any of
these studs are damaged, the heat exchanger must be replaced. Use of a short 10 mm box wrench will
reduce the risk of damaging these studs.
XIII. Service and Maintenance
(continued)
Summary of Contents for K2WT
Page 82: ...82 107110 01 6 16 Figure 10 4 Proper Installation of Header Sensor X Wiring continued ...
Page 83: ...83 107110 01 6 16 X Wiring continued Figure 10 5 Internal Ladder Diagram ...
Page 84: ...84 107110 01 6 16 X Wiring continued ...
Page 85: ...85 107110 01 6 16 Figure 10 6 Internal Wiring Connections Diagram X Wiring continued ...
Page 95: ...95 107110 01 6 16 Lighting and Operating Instructions XI Start Up and Checkout continued ...
Page 140: ...140 107110 01 6 16 XV Repair Parts continued ...
Page 142: ...142 107110 01 6 16 XV Repair Parts continued ...
Page 146: ...146 107110 01 6 16 XV Repair Parts continued ...
Page 148: ...148 107110 01 6 16 XV Repair Parts continued ...
Page 161: ...161 107110 01 6 16 ...
Page 162: ...162 107110 01 6 16 ...
Page 163: ...163 107110 01 6 16 ...