156
107110-01 - 6/16
Warning
Failure to setup the Boiler in accordance with these instructions could result in high amount of Carbon
Monoxide to be produced which could result in death, serious injury, and/or reduced component life.
Warning
If installing K2WT-080 or K2WT-180, do not attempt to convert K2WT-080 for use with LP at altitudes above
2000 ft. Also, do not attempt to convert K2WT-180 for use with LP gas at altitudes above 7800 ft. Attempts
to do so may result in unreliable operation, property damage, personal injury or loss of life due to carbon
monoxide (CO) poisoning.
Warning
LP Conversions - K2WT boiler setup from factory is configured for use with natural gas installed from 0 -
2000 ft above sea level only. For conversion to LP at altitude above 2000 ft., please follow these specific
instructions before converting for use with LP. If the information in these instructions is not followed
exactly, a fire, an explosion or production of carbon monoxide may result causing property damage,
personal injury or loss of life. The qualified service agency is responsible for proper installation of this
boiler for use with LP gas. The installation is not proper and complete until the operation of the converted
appliance is checked as specified in the manufacturer’s instructions supplied.
Adjusting Boiler Type (must be completed first)
Select the correct K2WT boiler size and altitude range using
the touch screen display as follows:
1. Check boiler’s label for actual boiler size.
2. Confirm installation altitude
3. Power up the boiler. The display will show the
Home screen.
4. Press “Adjust” button on the Home screen.
5. Press “Adjust” button on the Adjust Mode screen.
6. Press “Login” button to access Password screen.
7. Press 5-digit display to open a keypad.
Enter the
password “86”
and press the return arrow to close
keypad. Press “Save” button.
8. Press “Adjust” button to enter Adjustment Mode.
9. Press “Modulation Setup” menu button.
10. Press “Adjust” button on the Boiler Type screen.
11. Use the ↓ ↑ arrow buttons to select the correct size
and
altitude of your boiler. Press the (Check with
Circle) button to enter your selection.
12. Press “Enter” button until display stops blinking,
press next and repeat until “Completed” is
displayed.
13. Press X to exit
Basic Setup Procedure for K2WT High Altitude
Natural Gas
1. Start and force to hi fire
2. Measure CO
2
and bring into window via throttle
screw
3. Measure CO, if less than <150 ppm boiler can be
placed into service
These instructions apply only to the following K2WT boiler configurations:
2001 ft.- 4500 ft, 4501 ft.- 7800 ft., 7801
ft.- 10,100 ft.
These instructions contain specific information to setup your boiler to ensure proper
operation.
Appendix B: Instructions for High Altitude Installations Above 2000 ft.
DangEr
These instructions include a procedure for adjusting the air-fuel mixture on this boiler. This procedure
requires a combustion analyzer to measure the CO
2
(or Oxygen) and Carbon Monoxide (CO) levels in flue
gas. Adjusting the air-fuel mixture without a proper combustion analyzer could result in unreliable boiler
operation, personal injury, or death due to carbon monoxide poisoning.
Summary of Contents for K2WT
Page 82: ...82 107110 01 6 16 Figure 10 4 Proper Installation of Header Sensor X Wiring continued ...
Page 83: ...83 107110 01 6 16 X Wiring continued Figure 10 5 Internal Ladder Diagram ...
Page 84: ...84 107110 01 6 16 X Wiring continued ...
Page 85: ...85 107110 01 6 16 Figure 10 6 Internal Wiring Connections Diagram X Wiring continued ...
Page 95: ...95 107110 01 6 16 Lighting and Operating Instructions XI Start Up and Checkout continued ...
Page 140: ...140 107110 01 6 16 XV Repair Parts continued ...
Page 142: ...142 107110 01 6 16 XV Repair Parts continued ...
Page 146: ...146 107110 01 6 16 XV Repair Parts continued ...
Page 148: ...148 107110 01 6 16 XV Repair Parts continued ...
Page 161: ...161 107110 01 6 16 ...
Page 162: ...162 107110 01 6 16 ...
Page 163: ...163 107110 01 6 16 ...