28
107110-01 - 6/16
Option
18
19
20
21
Illustrated in Figure
7.19
7.19
7.20
7.20
Pipe Penetration
Through Structure
Vent
Roof
Roof
Roof
Roof
Intake
Roof
Roof
Roof
Roof
Material
Vent
DuraVent
PolyPro
(Rigid/Flex)
DuraVent
PolyPro
(Rigid/Flex)
Centrotherm
InnoFlue
SW/Flex
Centrotherm
InnoFlue
SW/Flex
Intake
B Vent/PVC
B Vent/PVC
B Vent/PVC
B Vent/PVC
Nominal Diameter
Vent
2”
3”
2”
3”
Intake
2” or 3”
3”
2” or 3”
3”
Min B Vent ID
5”
6”
5”
6”
Min Equivalent Vent Length:
Models
K2WT-080
36”
36”
36”
36”
K2WT-100
36”
36”
36”
36”
K2WT-120
Not Permitted
36”
Not Permitted
36”
K2WT-150
52”
52”
K2WT-180
52”
52”
Max Equivalent Vent Length (Note 1):
Models
K2WT-080
60ft
135ft
60ft
135ft
K2WT-100
60ft
135ft
60ft
135ft
K2WT-120
Not Permitted
135ft
Not Permitted
135ft
K2WT-150
135ft
135ft
K2WT-180
135ft
135ft
Vent Manufacturer’s PN for Flex
Termination/Components Required
2PPS-VFT
2PPS-BV*
2PPS-FLEX**
3PPS-VFT
3PPS-BV*
3PPS-FLEX**
IFBK02****
IAWP02B
IFBK03****
IAWP03B
* Specify size of B vent (e.g. 2PPS-BV
6
is for use with 6” B vent)
** Specify length in feet.
**** Specify Flex length and B-vent diameter (e.g. IFBK02
2505
includes 25ft of flex and used with 5” B vent)
Note 1: Max vent lengths shown also apply to the intake. Flex vent reduces the maximum allowable vent length.
See equivalent lengths for flex vent shown in Table 7.14 and sizing example on page 30.
Vii. Venting
C. Design Requirements Unique to Vertical Venting Systems (continued)
Table 7.13b: Summary of Vertical “B-Vent Air Chase” Vent Options
(B-Vent Chase MUST Be Sealed)
nOTiCE
Vertical venting and combustion air roof penetrations (where applicable) require the use of roof flashing
and storm collar, which are not supplied with the boiler, to prevent moisture from entering the structure.
Summary of Contents for K2WT
Page 82: ...82 107110 01 6 16 Figure 10 4 Proper Installation of Header Sensor X Wiring continued ...
Page 83: ...83 107110 01 6 16 X Wiring continued Figure 10 5 Internal Ladder Diagram ...
Page 84: ...84 107110 01 6 16 X Wiring continued ...
Page 85: ...85 107110 01 6 16 Figure 10 6 Internal Wiring Connections Diagram X Wiring continued ...
Page 95: ...95 107110 01 6 16 Lighting and Operating Instructions XI Start Up and Checkout continued ...
Page 140: ...140 107110 01 6 16 XV Repair Parts continued ...
Page 142: ...142 107110 01 6 16 XV Repair Parts continued ...
Page 146: ...146 107110 01 6 16 XV Repair Parts continued ...
Page 148: ...148 107110 01 6 16 XV Repair Parts continued ...
Page 161: ...161 107110 01 6 16 ...
Page 162: ...162 107110 01 6 16 ...
Page 163: ...163 107110 01 6 16 ...