97
107110-01 - 6/16
7. Warm Weather Shutdown (WWSD)
Some boilers are used primarily for heating buildings,
and the boilers can be automatically shutdown when
the outdoor air temperature is warm. When outside air
temperature is above the WWSD setpoint, this function
will shut down the boiler, boiler and system pump.
8. Energy Management System (EMS) Interface
A factory configured RS485 Modbus interface is
available for Energy Management System (EMS)
monitoring when not used for Multiple Boiler
Sequencer Peer-To-Peer Network. Consult factory for
points list or if this interface must be used in addition
to the boiler Peer-to-Peer Network.
9. Circulator Control
The Control may be used to sequence the domestic
hot water, boiler and system circulators. Service rated
relay outputs are wired to a line voltage terminal block
for easy field connection. Simple parameter selections
allow all three pumps to respond properly to various
hydronic piping arrangements including either a boiler
or primary piped indirect water heater. Circulators may
be configured to provide the functionality of a two zone
zone panel. The system and DHW pump outputs may
be configured as one heating and one domestic or two
heating zones. Circulators are automatically run for
a 20 second exercise period after not being used for
longer than 7 days. Circulator exercise helps prevent
pump rotor seizing.
10. Multiple Boiler Sequencer Peer-To-Peer
Network
The Control includes state-of-the-art modulating lead-
lag sequencer for up to eight (8) boilers capable of auto
rotation, outdoor reset and peer-to-peer communication.
The peer-peer network is truly “plug and play”.
Communication is activated by simply connecting
a RJ45 ethernet cable between boilers. The Control
provides precise boiler coordination by sequencing
boilers based on both header water temperature and
boiler modulation rate. For example, the lead boiler
can be configured to start a lag boiler after operating
at 50% modulation rate for longer than an adjustable
time. The boilers are modulated in “unison” (parallel)
modulation rate to ensure even heat distribution.
XII. Operation
(continued)
B. Supply Water Temperature Regulation
1. Priority Demand
The Control accepts a call for heat (demand) from
multiple places and responds according to it’s
“Priority”. When more than 1 demand is present the
higher priority demand is used to determine active
boiler settings. For example, when Domestic Hot
Water (DHW) has priority the setpoint, “Diff Above”,
“Diff Below” and pump settings are taken from DHW
selections. Active “Priority” is displayed on the “Boiler
Status” screen.
Priority Status Screen
Display
Boiler Responding to:
1st
Sequencer
Control
The boiler is connected to the peer-
to-peer network. The boiler accepts
demand from the Sequencer Master.
2nd
Domestic Hot
Water
DHW call for heat is on and selected
as the priority demand. DHW is
always higher priority than Central
Heat. It also has higher priority than
the Sequencer Control when DHW
priority is “enabled” and “Boiler
Piped” IWH is selected.
3rd
Central Heat
Central Heat call for heat is on and
there is no DHW demand or DHW
priority time has expired.
4th
Auxiliary Heat
Auxiliary Heat call for heat is on and
there is no Central Heat or DHW
demand. (NOTE: May be user
selected to be higher priority than
Central Heat.)
5th
Frost
Protection
Frost Protection is active and there
is no other call for heat. Frost
protection will be a higher priority
than Sequencer Control if the
Sequence Master has no active call
for heat.
6th
Warm
Weather
Shutdown
(WWSD)
WWSD is active and the boiler
will not respond to central heat
demands. DHW demand is not
blocked by WWSD.
7th
Standby
There is no demand detected.
Table 12.1: Order of Priority
2. Setpoint Purpose
The Control starts and stops the boiler and modulates
the boiler input from minimum (MBH) to maximum
(MBH) in order to heat water up to the active setpoint.
The setpoint is determined by the priority (Central
Heat or Domestic Hot Water) and as described in the
following paragraphs.
3. Central Heat Setpoint
Upon a Central Heat call for heat the setpoint is
either the user entered Central Heat Setpoint, or is
automatically adjusted by Outdoor Air Reset or, an
Energy Management System (EMS) supplied setpoint.
4. Auxiliary Heat Setpoint
Auxiliary Heat is a second heating demand that may
be used to serve either lower temperature radiation
or warmer heat demands such as fan coils. Upon an
Auxiliary Heat call for heat the setpoint is either the
user entered Auxiliary Heat Setpoint or is automatically
adjusted as Outdoor Air Reset
.
Summary of Contents for K2WT
Page 82: ...82 107110 01 6 16 Figure 10 4 Proper Installation of Header Sensor X Wiring continued ...
Page 83: ...83 107110 01 6 16 X Wiring continued Figure 10 5 Internal Ladder Diagram ...
Page 84: ...84 107110 01 6 16 X Wiring continued ...
Page 85: ...85 107110 01 6 16 Figure 10 6 Internal Wiring Connections Diagram X Wiring continued ...
Page 95: ...95 107110 01 6 16 Lighting and Operating Instructions XI Start Up and Checkout continued ...
Page 140: ...140 107110 01 6 16 XV Repair Parts continued ...
Page 142: ...142 107110 01 6 16 XV Repair Parts continued ...
Page 146: ...146 107110 01 6 16 XV Repair Parts continued ...
Page 148: ...148 107110 01 6 16 XV Repair Parts continued ...
Page 161: ...161 107110 01 6 16 ...
Page 162: ...162 107110 01 6 16 ...
Page 163: ...163 107110 01 6 16 ...