APPENDIX A: BOILER MENU ITEM DESCRIPTIONS – Continued
MENU LEVEL & OPTION
DESCRIPTION
CONFIGURATION MENU (Cont.)
Aux Start On Dly
Specifies the amount of time to wait (0 to 120 sec.)
between activating the Aux Relay (due to a demand) and
checking the pre-purge string to start the boiler. Default
is 0 sec.
Failsafe Mode
Allows the Failsafe mode to be set to either Constant
Setpoint or Shutdown. Default is Shutdown.
Analog Output
Must be set to Valve Pos 0-10V for BMK 750 & 1000.
Lo Fire Timer
Specifies how long (2 to 600 sec.) to remain in the low
fire position after ignition, before going to the desired
output. Default is 2 sec.
Setpt Limiting
Setpoint Limiting can be Enables or Disablled. The
default setting is Enabled.
Setpt Limit Band
The Setpoint Limit Band can be set from 0 to 10. The
default setting is 5.
Network Timeout
Specifies the timeout value (seconds) before a Modbus
fault is declared. Available settings range from 5 to 999
seconds. Default is 30 seconds.
Shutoff Dly Temp
This feature delays the shutdown of a boiler in order to
reduce excessive cycling. This specifies the temperature
value the Outlet Temperature is permitted to rise above
setpoint before being shut down.
Span is 0 to 25, Default is 10.
Demand Offset
This entry will reduce excessive ON/OFF cycling in
AUTO mode. When this entry is a non-zero value, the
unit will not turn on again until
Valve Position In
reaches
the Start Level value AND the Outlet Temperature goes
below the
Active Setpoint – Demand Offset.
In addition,
the boiler will fire at the 29% Valve Position level or
below for a period of one minute.
When this entry is set to zero, the unit will turn on again
as soon as the
Valve Position in
reaches the
Start Level
value. There will not be a one minute delay when firing at
the 29% Valve Position level.
Setting range is 0 to 25. (Default is 10)