Benchmark 750/1000 Boiler
CHAPTER 10. BOILER SEQUENCING TECHNOLOGY
Page
128
of
192
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0082_0J
05/21/2014
Ph.: 800-526-0288
GF-130
Option 3 –
Continued
Step 3 - Configure ALL C-More Units
On ALL Boilers
:
1. Go to the
Configuration Menu
and set the
BST Menu
item to
Enabled
.
2. Go to the
BST Menu
and set the
BST Mode
item to
BST Slave
(for now).
On MASTER only
:
3. Go to the
BST Setpoint
item and enter the Failsafe Setpoint.
4. Go to the
BST Setup Menu
item and set to
Enabled
.
5. Go to the
BST Setpoint Mode
item and select
Outdoor Reset
.
6. Go to the
Head Temp Source
item
and select
FFWD Temp
.
7. Go to the
BST Outdoor Sens
item and select
Enabled
.
8. Go to the
Outdoor Temp Source
item and select
Outdoor Temp
.
When ALL C-More units have been configured
:
9. Go to the
BST Menu
of the desired
Master
unit
and set the
BST Mode
item to
BST
MASTER
.