CHAPTER 10. BOILER SEQUENCING TECHNOLOGY
OMM-0082_0J
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
137
of
192
GF-130
Ph.: 800-526-0288
05/21/2014
Option 8 – Continued
Step 3: Configure ALL C-More Units
On ALL Boilers:
1. Go to the
Configuration Menu
and set the
BST Menu
item to
Enabled
.
2. Go to the
BST Menu
and set the
BST Mode
item to
BST Slave
(for now).
On MASTER only:
3. Go to the
BST Setpoint
item and enter the failsafe Setpoint.
4. Go to the
BST Setup Menu
item and set to
Enabled
.
5. Go to the
BST Setpoint Mode
item and select Remote
Setpoint
.
6. Go to the
BST Remote Signal
and select either
Network
.
7. Go to the
Head Temp Source
item and select
Network
.
8. Go to the
Header Temp Addr
item and
enter the Modbus Address (240).
9. Go to the
Header Temp Point
item and enter the Modbus Point (14).
When ALL C-More units have been configured:
10. Go to the
BST Menu
of the desired
Master
unit
and set the
BST Mode
item to
BST
MASTER
.