Benchmark 750/1000 Boiler Installation, Operation & Maintenance Manual
APPENDIX J – RECOMMENDED PERIODIC TESTING
Page
180
of
192
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0082_0J
05/21/2014
Ph.: 800-526-0288
GF-130
Item
Frequency
Accomplished
By
Remarks
Low air flow
Monthly
Operator
See section 6.8
High and low gas
pressure interlocks
Monthly
Operator
See sections 6.2 and 6.3
Air/Fuel Valve purge
position switch
Annually
Service
Technician
See section 6.10
Air/Fuel Valve ignition
position switch
Annually
Service
Technician
See section 6.11
Safety valves
As required
Operator
Check per A.S.M.E. Boiler and Pressure
Vessel Code, Section IV
Inspect burner
components
Semi-
Annually
Service
Technician
See section 7.7
Condensate Trap
Semi-
Annually
Operator
See section 7.8
Oxygen (O
2
) Level
Monthly
Operator
Verify oxygen level is between 3% and 8%
during boiler operation