Clamp-on Ground Resistance Tester Model 6417
21
Menu # Indication
Function
11
HOLd
Enabling/Disabling the AUTO-HOLD Mode:
■ Enter the menu by ►.
HOLd
blinks.
■ Press ▲ or ▼ to switch the AUTO-HOLD mode to
active or inactive.
-
AUTO-HOLD Mode Disabled:
Only the
icon is displayed.
-
AUTO-HOLD Mode Enabled:
The
and
icons are displayed.
■ Validate and return to the previous menu by ►.
12
VER
Displaying the version number
■ Enter the menu by ►.
■
The version number is displayed.
■ Return to the previous menu by ►.
13
CAL
Reserved for factory use - not used for normal
operation
4.5 Calibration Loop
The provided 5Ω calibration test loop (Figure 4-2) lets you perform a quick check
of the instrument’s accuracy. To do this, turn ON the instrument and wait until
it completes its startup calibration cycle. Then clamp the instrument around
the loop; the measurement should read between 4.8Ω and 5.2Ω. If not, clean
the instrument and repeat the measurement. If you are still unable to obtain a
measurement between 4.8Ω and 5.2Ω, contact AEMC.