24
Clamp-on Ground Resistance Tester Model 6417
5.5 Turning Bluetooth ON
1. Rotate the rotary switch to the MR or Setup position.
2. Press and release the
HOLD /
button.
■
When Bluetooth (BT) is ON the Bluetooth icon ( ) appears at the bottom of
the display. This icon is steady when Bluetooth is enabled but not connected
to the computer, and blinks when connection is established.
■
To turn Bluetooth OFF, repeat the steps 1 and 2.
■
Once Bluetooth is ON you can rotate the rotary switch to any position (except
OFF) and the Bluetooth will remain ON.
5.6 Turning the Instrument OFF
The instrument can be turned OFF in two ways:
■
Manually:
Turn the rotary switch to
OFF
.
■
Auto Power OFF:
This function activates after 5 minutes of no activity (no
button press, no change of switch setting, and no opening of the jaws).
-
Fifteen seconds before Auto Power OFF, a short audible signal is emitted
and the display blinks once a second.
Auto Power OFF can be disabled in
SET-UP
(see
§
4.4, menu #3). The
symbol is then displayed.
5.7 Standard and Advanced Modes
The instrument has two modes.
■
Standard Mode:
Makes the standard loop resistance and leakage current
measurements.
■
Advanced Mode:
Used to refine and complete the measurements:
-
Impedance at the selected frequency.
-
Contact voltage.
-
Resistive and inductive components of the loop impedance.
The choice of Standard or Advanced mode and the alarm thresholds are
configured in
SET-UP
(see
§
www.
GlobalTestSupply
.com
Find Quality Products Online at: