- 45 / 50 -
BN 09 2671/01/01
10 MAINTENANCE
AEG Power Solutions can provide a Global Service capability through regional Service Centres.
Electronic boards are sensitive to E.S.D. (electrostatic discharge).
When not installed in the equipment, they are delivered in antistatic bags.
Before handling a board, the operator must take care to be at the same potential as the
equipment to be worked on and take all customary precautions.
ANY OPERATION ON THE EQUIPMENT SHOULD BE CARRIED OUT BY QUALIFIED
PERSONNEL AWARE OF SPECIFIC ELECTRICAL HAZARDS AND PRECAUTIONS TO
BE TAKEN. NEVER ASSUME THE ABSENCE OF VOLTAGE, ALWAYS CHECK WITH
A VOLTMETER BEFORE ANY OPERATION ON A SYSTEM.
THE DC OUTPUT IS EQUIPPED WITH FILTERING CAPACITORS, DANGEROUS
VOLTAGES CAN REMAIN EVEN IF THE CHARGER IS STOPPED AND THE BATTERY
DISCONNECTED. ALWAYS CHECK THE ABSENCE OF VOLTAGE ON THE DC
CIRCUITS BEFORE TO START ANY WORKS ON THE SYSTEM.
DANGEROUS VOLTAGES CAN REMAIN ON THE SYSTEM EVEN IF IT IS SWITCHED
OFF AND INSULATED FROM MAINS AS LONG AS BATTERY IS CONNECTED.
10.1 PREVENTIVE MAINTENANCE VISIT
It is recommended to perform a maintenance visit every year.
10.1.1 Rectifier maintenance
Remove dust.
Carry out an inspection including the following:
1 - Disconnect the mains input line and the battery.
2 - Examine the components and the wiring. Pay special attention to signs of overheating and melted insulation.
Check all connections. Check for loose wires.
3 - Check that the cooling air flow is not impeded, clean the fans, the air inlets and outlets in case of presence of
dust.
4 - For rectifiers with air inlet filters (on the door and/or on the roof), check the filters for cleanliness.
5 - Check the operation of the rectifier and the voltage levels
(see customer drawings)
.
6 - The GCAU board is equipped with a lithium battery for the Real Time Clock (RTC). This component has a life
time of about 10 years. Its replacement must be done by specialized personnel.
IMPORTANT
This component, mounted on a support, must be recycled in compliance with the European Directive
n° 91/157/EEC of 18.03.91. You can also apply to AEG Power Solutions by shipping back the used
board (prepaid shipment).
10.1.2 Battery maintenance
For the recommended battery maintenance procedures, refer to the battery manufacturer’s manual.
At the end of their service life, the batteries must be recycled in compliance with the European Directive
n° 91/157/EEC of 18.03.91 and WEEE directive. You can also apply to the battery manufacturer as indicated in the
battery manual.