6.6.3 How to activate Manual Floating Charge
When you are in high rate or commissioning charge mode, you can manually switch the rectifier in the floating
charge mode. Follow the instructions below
.
or
Starting from the main menu, select
‘Cmnd’
.
Press
‘Next’
until the following indication is displayed:
6.6.4 Manual Voltage and Current adjustment (OPTION)
If required, your system can be programmed as a power supply. It allows you to adjust the output voltage and
output current over a wide range. Both functions can be activated independently.
When only the output current adjustment is activated, the output voltage is the voltage of the current charge
(floating, highrate, commissioning).
Warning:
Do not activate this option when the charger is used for normal battery charging. Consult the nearest agent of your
system if you want to use this option. Activating this option without the necessary system knowledge can damage
the connected battery.
The rectifier operates as a power supply only. It delivers the adjusted voltage and, if activated, the manually adjusted
current. If the manual current adjustment is not activated the current limit is as specified on the nameplate of your
system.
The voltage adjustment is configured to operate within a window.
HIGHRATE CHARGE
Monit Confg
Cmnd
COMMISSIONING
Monit Confg
Cmnd
SET FLOATING
Next
Enter
Exit
Start Floating?
Yes Cancel
Press
‘Enter’
..
Floating charge can be switched on by hitting the
‘Yes’
key