6.6.7 How to reset Ah Meter (OPTION)
Starting from the main menu, select
‘Cmnd’
.
Select ‘
Next
’ until the following menu is displayed.
Press
‘Enter’
.
A Supervisor or User level password is required to continue.
With the right pointing arrow
'
'
the digit position can be selected and with the arrow up
'
'
an alphanumeric
character between 0 and 9 or between A and Z can be set. If all four characters are set, press
‘Enter’
.
When the password is correct, the display switches to the
‘Ah Meter = 100’
Yes/No selection. If the password is
incorrect a message
‘WRONG PASSWORD’
is displayed for two seconds and the menu jumps one position back
in the menu tree.
Reset Ah meter by pressing the
‘Yes’
key initiates the battery Ah counter to 100% and causes a jump to the default
menu. Pressing
‘No’
or
‘Cancel’
will cause a jump to
‘AH METER = 100’
menu.
This manipulation must be always done before a manual battery test.
6.6.8 How to Adjust the Display Contrast
Adjusting the Contrast from the Default Menu :
When the contrast is too low to read the display, the contrast can be adjusted directly from the default menu. If the
leftmost button from the default menu is held, the contrast will be decreased. If the rightmost button from the default
menu is held, the contrast will be increased. If you are not sure whether the default menu is displayed, do not touch
any button for 5 minutes. This will automatically activate the default menu.
FLOATING CHARGE
Monit Confg
Cmnd
AH METER = 100
Next
Enter
Exit
Password: 1111
Enter
Ah Meter = 100
Yes No Cancel
Correct password
WRONG PASSWORD