- 49 / 50 -
BN 09 2671/01/01
ALARM or EVENT
PROBABLE CAUSE
CORRECTIVE ACTION
“INTERNAL CHECK”
Communication error between the
microcontrollers or internal system error
(e.g.: DC overvoltage protection,
synchro pulse missed, TPC board error
… etc.)
Call the customer service
department.
“LONG CHARGE TIME”
High rate charge time too long.
Call the customer service
department.
“NO PS VOLTAGE”
No more DC power supply to the board:
rectifier output voltage out of order
. Check the fuse F1.
. Call the customer service
department.
“CHARGER OFF”
It can be due to a normal
system operation.
. Alarm activation.
. Serial information input.
. Manual shutdown.
. Initialising delay.
. Put the rectifier in floating charge
mode.
. Call the customer service
department to identify bad system
configuration.