6.6.2 How to Activate Manual Commissioning Charge
The Manual Commissioning charge is a command function and is located under the Command (
‘Cmnd’
) key. To
prevent accidental activation, this command can be password protected if required.
Follow the instructions below.
Press
‘Next’
until the following indication is displayed:
Press ‘
Enter
’.
With the right pointing arrow
'
'
the digit position can be selected and with the arrow up
'
'
an alphanumeric
character between 0 and 9 or between A and Z can be set. When all four characters are set, press
‘Enter’
.
If the password is correct the display switches to the Commissioning on/off selection.
Incorrect passwords will cause a jump of one position back in the menu tree and a message
‘WRONG
PASSWORD’
is displayed.
If no password is activated the Commissioning selection menu will be shown directly.
With
‘Yes’
, the Commissioning charge can be switched on.
To stop the commissioning charge, the user can manually put the rectifier in floating charge mode via the command
menu (see paragraph 6.6.3) or wait for the timer times out. In this last case, the rectifier switches automatically in
floating charge mode.
The remaining commissioning charge time can be read on the LCD display via the measurements menu. See
paragraph 6.5.1.
FLOATING CHARGE
Monit Confg
Cmnd
SET COMMISSION.
Next
Enter
Exit
Set Commission.?
Yes Cancel
Password: 1111
Enter
Correct password
WRONG PASSWORD
Starting from the main menu, select
‘Cmnd’
.