6.6.6 How to Clear the Event and Alarm History List
If required, the event and alarm history list of your system can be cleared from the front panel. A password on
Supervisor or User level is mandatory to clear the list.
Follow the instructions below.
Starting from the main menu, select
‘Cmnd’
.
Select ‘
Next
’ until the following menu is displayed.
Press ‘
Enter
’.
A Supervisor or User level password is required to continue.
With the right pointing arrow
'
'
the digit position can be selected and with the arrow up
'
'
an alphanumeric
character between 0 and 9 or between A and Z can be set. If all four characters are set, press
‘Enter’
.
When the password is correct, the display switches to the Clear History Yes/No selection. If the password is
incorrect, a message
‘WRONG PASSWORD’
is displayed for two seconds and the menu jumps one position back
in the menu tree.
Clear the History list by pressing the
‘Yes’
key. Pressing
‘No’
will cause a jump two menus back.
FLOATING CHARGE
Monit Confg
Cmnd
CLEAR HISTORY
Next
Enter
Exit
Password: 1111
Enter
Clear History ?
Yes No Cancel
Correct password
WRONG PASSWORD