Changing Configuration to Modbus Protocol
H-2 ADAM 4000 Series User’s Manual
The ADAM-4000 Modbus version modules may come from the
factory set for which ADAM ASCII protocol are set as the default
protocol.
If the module is connected to a Modbus network, the Modbus
network may not recognize the module. This may be caused by
the incorrect settings. ADAM-4000 module should be set-up for
Modbus protocol instead of ADAM ASCII protocol.
Please follow the steps as below for configuring an ADAM-4000
module to Modbus protocol.
1.
Configure the ADAM-4000 Module with the ADAM-4000 utility
(latest ADAM-4000 utility can be found at
www.advantech.com
service & support.)
2.
Initialize the ADAM-4000 on a RS-485 network (the preferred
method is one module at a time on the RS-485 network).
3.
With the module powered off, turn the switch in the “Init” position.
(For some older Adam models, use an external wire to connect the
INIT* terminal to the GND terminal)
4.
Power up the module
5.
Wait 10 seconds for the module to initialize.
6.
Using the ADAM-4000 utility, search (scan) for the module to
change the protocol. (Initial COM settings: 9600 baud, N-8-1)
7.
The utility will identify the module from the search function.
8.
The ADAM-4000 utility will now permit the serial data protocol to
be changed to the Modbus protocol.
9.
The address and COM port settings can also be changed at this time.
10.
To access the module, click on the module icon in the utility.
11.
Update the settings by pressing the “Update” button.
12.
Power off the module.
13.
Turn the switch back to NORMAL* position. (For the older Adam
models, remove the wire between the INIT* and GND terminals)
14.
The module is now ready to be placed in the Modbus network.
Summary of Contents for Data Acquisition Modules ADAM 4000
Page 1: ...ADAM 4000 Data Acquisition Modules User s Manual ...
Page 7: ...Introduction 1 ...
Page 11: ...Installation Guideline 2 ...
Page 28: ...I O Modules 3 ...
Page 98: ...Chapter 3 Chapter 3 I O Modules 3 71 Figure 3 69 ADAM 4069 Form A Relay Output ...
Page 104: ...Command Set 4 ...
Page 147: ...Analog Input Module Command Set 5 ...
Page 215: ...Analog Output Module Command Set 6 ...
Page 236: ...Digital I O Relay ouput and Counter Frequency Command Set 7 ...
Page 313: ...Calibration 8 ...
Page 329: ...Technical Specifications A ...
Page 335: ...Appendix A Appendix A Technical Specification A 7 Figure A 2 ADAM 4011D Function Diagram ...
Page 337: ...Appendix A Appendix A Technical Specification A 9 Figure A 3 ADAM 4012 Function Diagram ...
Page 339: ...Appendix A Appendix A Technical Specification A 11 Figure A 4 ADAM 4013 Function Diagram ...
Page 341: ...Appendix A Appendix A Technical Specification A 13 Figure A 5 ADAM 4016 Function Diagram ...
Page 343: ...Appendix A Appendix A Technical Specification A 15 Figure A 6 ADAM 4017 4017 Function Diagram ...
Page 349: ...Appendix A Appendix A Technical Specification A 21 Figure A 8 ADAM 4018M Function Diagram ...
Page 351: ...Appendix A Appendix A Technical Specification A 23 Figure A 9 ADAM 4019 Function Diagram ...
Page 355: ...Appendix A Appendix A Technical Specification A 27 Figure A 11 ADAM 4024 Function Diagram ...
Page 357: ...Appendix A Appendix A Technical Specification A 29 Figure A 12 ADAM 4050 Function Diagram ...
Page 377: ...Data Formats and I O Ranges B ...
Page 389: ...Technical Diagrams C ...
Page 392: ...Technical Diagrams C 4 ADAM 4000 Series User s Manual Figure C 3 DIN Rail Mounting ...
Page 394: ...Technical Diagrams C 6 ADAM 4000 Series User s Manual Figure C 5 Panel Mounting ...
Page 395: ...Appendix C Appendix C Technical Diagrams C 7 C 2 3 Piggyback Stack Figure C 6 Piggyback Stack ...
Page 396: ...Utility Software D ...
Page 404: ...RS 485 Network E ...
Page 411: ...How to use the Checksum feature F ...
Page 415: ...ADAM 4000 I O Modbus Mapping Table G ...
Page 428: ...Changing Configuration to Modbus Protocol H ...