Chapter
5
5-5
ADAM 4000 Series User’s Manual
4011, 4011D, 4012, 4013, 4015, 4015T, 4016,
4017, 4017+, 4018, 4018+, 4018M, 4019+
%AANNTTCCFF
Response
!AA(cr)
if the command is valid.
?AA(cr)
if an invalid parameter was entered or if the INIT*
terminal was not grounded when attempting to change baud
rate or checksum settings.
There is no response if the module detects a syntax error or
communication error or if the specified address does not
exist.
!
delimiter character indicates a valid command was
received.
? delimiter character indicates the command was invalid
AA
(range 00-FF) represents the 2-character hexadecimal
address of an analog input module.
(cr)
is the terminating character, carriage return (0Dh)
Example
command:
%2324050600(cr)
response: !24(cr)
The ADAM-4011 module with address 23h is configured to
a new address of 24h, an input range ±2.5 V, baud rate
9600, integration time 50 ms (60 Hz), engineering units
data format and no checksum checking or generation.
The response indicates that the command was received.
Wait 7 seconds to let the new configuration settings take
effect before issuing a new command to the module.
NOTICE: Only ADAM-4011, ADAM-4011D, ADAM-4012, ADAM-4013,
ADAM-4016 and ADAM-4018+ support “% of FSR” and “two’s
complement of hexadecimal” Data Format.
NOTICE: An analog input module requires a maximum of 7 seconds to
perform auto calibration and ranging after it is reconfigured.
During this time span, the module cannot be addressed to
perform any other actions.
NOTICE:
All configuration parameters can be changed dynamically,
except checksum and baud rate parameters. They can only be
altered when the INIT* terminal is grounded. (Refer to Baud
rate and Checksum configuration in Chapter 2,
for the correct
procedure)
Summary of Contents for Data Acquisition Modules ADAM 4000
Page 1: ...ADAM 4000 Data Acquisition Modules User s Manual ...
Page 7: ...Introduction 1 ...
Page 11: ...Installation Guideline 2 ...
Page 28: ...I O Modules 3 ...
Page 98: ...Chapter 3 Chapter 3 I O Modules 3 71 Figure 3 69 ADAM 4069 Form A Relay Output ...
Page 104: ...Command Set 4 ...
Page 147: ...Analog Input Module Command Set 5 ...
Page 215: ...Analog Output Module Command Set 6 ...
Page 236: ...Digital I O Relay ouput and Counter Frequency Command Set 7 ...
Page 313: ...Calibration 8 ...
Page 329: ...Technical Specifications A ...
Page 335: ...Appendix A Appendix A Technical Specification A 7 Figure A 2 ADAM 4011D Function Diagram ...
Page 337: ...Appendix A Appendix A Technical Specification A 9 Figure A 3 ADAM 4012 Function Diagram ...
Page 339: ...Appendix A Appendix A Technical Specification A 11 Figure A 4 ADAM 4013 Function Diagram ...
Page 341: ...Appendix A Appendix A Technical Specification A 13 Figure A 5 ADAM 4016 Function Diagram ...
Page 343: ...Appendix A Appendix A Technical Specification A 15 Figure A 6 ADAM 4017 4017 Function Diagram ...
Page 349: ...Appendix A Appendix A Technical Specification A 21 Figure A 8 ADAM 4018M Function Diagram ...
Page 351: ...Appendix A Appendix A Technical Specification A 23 Figure A 9 ADAM 4019 Function Diagram ...
Page 355: ...Appendix A Appendix A Technical Specification A 27 Figure A 11 ADAM 4024 Function Diagram ...
Page 357: ...Appendix A Appendix A Technical Specification A 29 Figure A 12 ADAM 4050 Function Diagram ...
Page 377: ...Data Formats and I O Ranges B ...
Page 389: ...Technical Diagrams C ...
Page 392: ...Technical Diagrams C 4 ADAM 4000 Series User s Manual Figure C 3 DIN Rail Mounting ...
Page 394: ...Technical Diagrams C 6 ADAM 4000 Series User s Manual Figure C 5 Panel Mounting ...
Page 395: ...Appendix C Appendix C Technical Diagrams C 7 C 2 3 Piggyback Stack Figure C 6 Piggyback Stack ...
Page 396: ...Utility Software D ...
Page 404: ...RS 485 Network E ...
Page 411: ...How to use the Checksum feature F ...
Page 415: ...ADAM 4000 I O Modbus Mapping Table G ...
Page 428: ...Changing Configuration to Modbus Protocol H ...