Appendix F
F.5 Grounding reference (Ground bar for the factory
environment should have a standard resistance
below 5
Ω
Ω
Ω
Ω
Ω
)
Since ADAM-4000 / 5000 system comes with a plastic outer case with
DC power supply, its grounding procedure should be done according
to the following points:
Ø
Power supply : The E terminal of the external power supply should
be connected with the panel.
Ø
The outer case of panel should be fixed with two grounding bus.
Connect the ground of power (E-terminal) to the grounding bus
with shortest path. Use single contact for connection.
Ø
Another grounding bus is for connection with AI and AO shielded
signal wires. While AI and AO signal wires enter inside the panel,
the shielding materials is stripped off and its copper mesh should
be entangled together (There is no effect leaving alone any single
wire strand). Connect to grounding bus in the shortest path, and
then connect the two grounding buses in a way such as the
following illustration: (Please note that wire length should not be
too long, otherwise it will compromise the quality of the twisted-
pair wires)
Figure F-5 : Grounding Reference
ADAM 5000/485
T/B
DC
P/S
E
AI
AO
E
Tr
Grounding Bus
Grounding Bus
Copper mesh for Shielding
(should be grounded only on one end)
Connect to ground bar on the factory.
The ground bar should have a resistance below 5 ohm.
Summary of Contents for ADAM-5510/P31
Page 17: ...0 Quick Start...
Page 38: ...0 22 ADAM 5510 P31 Quick Start...
Page 39: ...1 Introduction...
Page 43: ...2 Installation Guidelines...
Page 52: ...2 10 ADAM 5510 P31 Installation Guideline Figure 2 10 ADAM 5510 P31 network address DIP switch...
Page 58: ...2 16 ADAM 5510 P31 Installation Guideline...
Page 59: ...3 System Specifications...
Page 65: ...4 I O Modules...
Page 116: ...4 52 ADAM 5510 P31 I O Modules...
Page 117: ...ADAM 5510 P31 5 1 Chapter 5 5 Troubleshooting...
Page 129: ...ADAM 5510 P31 A 1 Appendix A A Quick Start Example...
Page 132: ...A 4 ADAM 5510 P31 Quick Start Example...
Page 133: ...ADAM 5510 P31 B 1 Appendix B B COM Port Register Structure...
Page 137: ...ADAM 5510 P31 C 1 Appendix C C Data Formats and I O Ranges...
Page 147: ...D Performance...
Page 173: ...E RS 485 Network...
Page 181: ...ADAM 5510 P31 F 1 Appendix F F ADAM 4000 5000 System Grounding Installation...
Page 187: ...ADAM 5510 P31 G 1 Appendix G G Grounding Reference...