ADAM-4000/5000 System Grounding Installation
Ø
The shielding material of the wires should only be grounded on
one end as illustrated in the following diagram. This is to avoid
ground loop.
Figure F-3: Grounding for on-site facilities and ADAM-5000/4000
Systems
Ø
Since shielded twisted-pair has been adopted for signal wires, only
DATA+ and DATA- of ADAM-5000 system should be connected.
And the shielding materials should be treated in the same manner
as with AI and AO signal wires, i.e. it should be connected to
Ground on only one end through the COM port on computer or on
ADAM-5000 system such as illustrated in the following diagram:
Figure F-4: Grounding for signal wires
AI
ADAM System
On-Site Facilities
Grounding
PC
Gounded only on one end
DATA+
DATA -
Summary of Contents for ADAM-5510/P31
Page 17: ...0 Quick Start...
Page 38: ...0 22 ADAM 5510 P31 Quick Start...
Page 39: ...1 Introduction...
Page 43: ...2 Installation Guidelines...
Page 52: ...2 10 ADAM 5510 P31 Installation Guideline Figure 2 10 ADAM 5510 P31 network address DIP switch...
Page 58: ...2 16 ADAM 5510 P31 Installation Guideline...
Page 59: ...3 System Specifications...
Page 65: ...4 I O Modules...
Page 116: ...4 52 ADAM 5510 P31 I O Modules...
Page 117: ...ADAM 5510 P31 5 1 Chapter 5 5 Troubleshooting...
Page 129: ...ADAM 5510 P31 A 1 Appendix A A Quick Start Example...
Page 132: ...A 4 ADAM 5510 P31 Quick Start Example...
Page 133: ...ADAM 5510 P31 B 1 Appendix B B COM Port Register Structure...
Page 137: ...ADAM 5510 P31 C 1 Appendix C C Data Formats and I O Ranges...
Page 147: ...D Performance...
Page 173: ...E RS 485 Network...
Page 181: ...ADAM 5510 P31 F 1 Appendix F F ADAM 4000 5000 System Grounding Installation...
Page 187: ...ADAM 5510 P31 G 1 Appendix G G Grounding Reference...