4-48
ADAM-5510/P31
I/O Modules
Overflow Value
Overflow value is the number of times the counter value exceeds the
Max/Min values you specified. When the counter value exceeds
Maximum value, the overflow value increases; When the counter value
goes under Minimum value, the overflow value decreases. Besides,
when the counter value runs beyond the range of Max/Min value, it
will continue counting from the initial value. Furthermore, if users want
to check the counter value to see if it is higher or lower than the Max/
Min value, they can run the "$aaSi7" command to gain a readout of the
overflow value.
Getting the Totalizer Value
If users want to get the actual counter value, a formula such as follows
can facilitate an easy calculation from the initial counter value,
overflow value and current counter value:
V
tol =
{|V
ini
-
V
min (or
V
max)
|+
1} x |V
vf
|
+ |V
ini
- V
cur
|
V
tol : totalizer value
V
ini : initial counter value
V
min : min. couner value = 0 (fixed value)
V
max : max. counter value = 2
32
= 4,294,967,295 (fixed value)
V
vf : overflow value
V
cur : current counter value
Example:
If the initial value =10, overflow value =4, min. value = 0, current
counter value = 3, the totalizer value could be calculated as
totalizer value = {|10 - 0| + 1} x| 4 |+ |10 -3| = 51
Summary of Contents for ADAM-5510/P31
Page 17: ...0 Quick Start...
Page 38: ...0 22 ADAM 5510 P31 Quick Start...
Page 39: ...1 Introduction...
Page 43: ...2 Installation Guidelines...
Page 52: ...2 10 ADAM 5510 P31 Installation Guideline Figure 2 10 ADAM 5510 P31 network address DIP switch...
Page 58: ...2 16 ADAM 5510 P31 Installation Guideline...
Page 59: ...3 System Specifications...
Page 65: ...4 I O Modules...
Page 116: ...4 52 ADAM 5510 P31 I O Modules...
Page 117: ...ADAM 5510 P31 5 1 Chapter 5 5 Troubleshooting...
Page 129: ...ADAM 5510 P31 A 1 Appendix A A Quick Start Example...
Page 132: ...A 4 ADAM 5510 P31 Quick Start Example...
Page 133: ...ADAM 5510 P31 B 1 Appendix B B COM Port Register Structure...
Page 137: ...ADAM 5510 P31 C 1 Appendix C C Data Formats and I O Ranges...
Page 147: ...D Performance...
Page 173: ...E RS 485 Network...
Page 181: ...ADAM 5510 P31 F 1 Appendix F F ADAM 4000 5000 System Grounding Installation...
Page 187: ...ADAM 5510 P31 G 1 Appendix G G Grounding Reference...