Unit Installation
ADTRAN 1748F Switch
22
Copyright © 2016 ADTRAN, Inc.
61700558F1-34B
Table 1. Fan Tray Specifications
To replace the fan tray, follow these steps:
Supplying Power to the Unit
This chapter focuses on the switch power supplies, how to install them, and how to power-on the switch.
Connecting the switch to ground is also covered.
This section includes these sections:
•
Power Supply Modules on page 22
•
Grounding the Chassis on page 23
•
Connecting to AC Power on page 24
Power Supply Modules
The switch supports hot-swappable power supply units (PSUs). You can install up to two PSUs with matching
airflow direction in the switch. The PSUs operate in a load-sharing mode and provide 1+1 redundancy.
Item
Description
Power Consumption
12 VDC @ 2.8 A, 37 Watts maximum
Airflow
76.4 CFM minimum
90.4 CFM maximum
Dimensions
207mm W x 94.25 mm D x 40.4 mm H
(8.15 inch W x 3.71 inch D x 1.59 inch H)
Replacing the Fan Tray
Step
Action
1
Loosen the two retaining screws on the front panel of the fan tray (see
2
Pull firmly on the screws until the fan tray is free.
3
Slide the fan tray out of the switch.
4
Insert the replacement fan tray into the slot and slide it slowly into the chassis.
5
Push firmly until the fan tray clicks into place. The fans should immediately start to operate.
6
Tighten the retaining screws to secure the fan tray in the chassis.
1+1 redundancy is a system where a switch power supply is backed up by another switch
power supply in a load-sharing mode. If one power supply fails, the other power supply
takes over the full load of the switch.
The switch includes plug-in power supply and fan tray modules that are installed into its
chassis. All installed modules must have a matching airflow direction. That is, all modules
must have a front-to-back (F2B) airflow direction, or all modules must have a
back-to-front (B2F) airflow direction. The airflow direction of PSUs and fan trays is
indicated by labels on the modules.
Summary of Contents for NetVanta 1748F Series
Page 8: ...Table of Contents ADTRAN 1748F Switch 8 Copyright 2016 ADTRAN Inc 61700558F1 34B...
Page 10: ...List of Figures ADTRAN 1748F Switch 10 Copyright 2016 ADTRAN Inc 61700558F1 34B...
Page 12: ...List of Tables ADTRAN 1748F Switch 12 Copyright 2016 ADTRAN Inc 61700558F1 34B...
Page 42: ...Troubleshooting ADTRAN 1748F Switch 42 Copyright 2016 ADTRAN Inc 61700558F1 34B...