Introduction
ADTRAN 1748F Switch
16
Copyright © 2016 ADTRAN, Inc.
61700558F1-34B
Forwarding Mode
• Store-and-forward
Throughput
• Wire speed
Flow Control
• Full Duplex: IEEE 802.3x
• Half Duplex: Back pressure
Environment
•
Operating Temperature: 0°C to 40°C (32°F to 140°F)
•
Storage Temperature: -40°C to 70°C (-40°F to 158°F)
•
Relative Humidity: Up to 95 percent, noncondensing
Physical
• Dimensions: 438.4 mm W x 473 mm D x 43.4 mm H (17.26 inch W x 18.62 inch H x 1.71 inch D)
• Weight: 8.395 kg (18.51 lb), with two installed power supply modules
Compliance
• FCC Part 15 Class A
• EN 55022:2010 Class A
• EN 61000-3-2:2009 Class A
• EN 61000-3-3:2008
• FCC Class A
• VCCI Class A
• CE Mark
• EN 55024:2010
• ICE 61000-4-2/3/4/5/6/8/11
• UL (CSA 22.2 No 60950-1 and UL 60950-1)
• CB (IEC/EN 60950-1)
Deployment
The switch is designed for high-availability environments with a high port density. The switch includes
redundant, hot-swappable, load-sharing AC PSUs, a hot-swappable fan tray, and port-to-power and
power-to-port airflow direction options. Meeting the network scaling requirements of enterprise and cloud data
centers, the switch can be deployed as a top-of-rack switch providing full line-rate switching at Layer 2 or
Layer 3 across all ports.
Rack Cooling
The top-of-rack switch is a high-performance, high-density unit that generates a substantial amount of heat.
When mounted in a rack with other equipment, it is important that the switch has the same airflow direction to
avoid
hot loops
in the data center aisles. Hot loops increase cooling requirements since warm air is drawn into
rack devices instead of cool air.
Most rack-mounted blade servers draw cool air from the front and expel hot air at the rear. The top-of-rack
switch includes power supply units and a fan tray module that have a front-to-back (F2B) airflow direction that
maintains cool aisles in the data center.
Summary of Contents for NetVanta 1748F Series
Page 8: ...Table of Contents ADTRAN 1748F Switch 8 Copyright 2016 ADTRAN Inc 61700558F1 34B...
Page 10: ...List of Figures ADTRAN 1748F Switch 10 Copyright 2016 ADTRAN Inc 61700558F1 34B...
Page 12: ...List of Tables ADTRAN 1748F Switch 12 Copyright 2016 ADTRAN Inc 61700558F1 34B...
Page 42: ...Troubleshooting ADTRAN 1748F Switch 42 Copyright 2016 ADTRAN Inc 61700558F1 34B...