38
36
Technical Specifications
5. 3rd stage indicator
6. 4th stage indicator
7. High temperature overheat indicator
8. Manual reset high limit thermostat
9. Control thermostat
Maximum Operating Pressure
Primary: 4 bar
Factory Test Pressure
Primary: 6 bar
Maximum Operating Temperature
90°C
* A dual element consists of two elements on a single flange, with a combined output of 4.8 kW at 230 volts
Control Panel
1
2
3
4
5
6
7
8
9
1. Thermometer
2. On/off switch
3. 1st stage indicator
4. 2nd stage indicator
TER
Rear
Front
Right Hand Side
TER 57
TER 86
TER 115
TER 144
TER 201
TER 259
Code
00080401
00080801
00081201
00081601
00079101
00079901
Maximum output
kW
57.6
86.4
115.2
144
201.6
259.2
Nominal supply
V
3 x 400 + N
Nominal supply (total)
amps
250.5
376
501
626
876.5
1127
Nominal supply (per phase)
amps
83.5
125.3
167
209
292
376
Dual heating elements *
#
12
18
24
30
42
54
Total capacity
L
155
155
155
155
250
250
Primary connection (female BSP)
Ø
2"
2"
2"
2"
DN100
DN100
Dimensions A
mm
80
80
80
80
80
80
B
mm
124
124
124
124
190
190
C
mm
1134
1134
1134
1134
1060
1060
D
mm
130
130
130
130
197
197
E
mm
610
610
610
610
752
752
F
mm
1380
1380
1380
1380
1380
1380
G
mm
610
610
610
610
752
752
Weight empty
Kg
102
102
102
102
195
195
Weight full
Kg
257
257
257
257
545
545