34
32
Technical Specifications
Maximum Operating Pressure
Primary:
3 bar
Secondary:
10 bar
Factory Test Pressure
Primary:
4.5 bar
Secondary:
13 bar
Maximum Operating Temperature
90°C
Note : The above performances are based on the hot water being blended at point of use, with a boiler
temperature of 85°C and a domestic cold water inlet of 10°C.
Domestic Hot Water Performances
E-Tech S
E-Tech S
E-Tech S
E-Tech S
E-Tech S
E-Tech S
160
240
290
290
380
380
Single Phase Single Phase
Single Phase
Tri-Phase
Single Phase
Tri-Phase
Code
00601001
00601101
00601201
00601201
00601301
00601301
Maximum output
kW
14.4
14.4
14.4
28.8
14.4
28.8
Nominal supply
V
230
230
230
3 x 400 + N
230
3 x 400 + N
Nominal supply
amps
63
63
63
3 x 42
63
3 x 42
Primary capacity
L
55
68
97
97
127
127
Total capacity
L
161
242
295
295
394
394
Heating surface area
m
2
1.26
1.87
2.0
2.0
2.6
2.6
DHW connection (male BSP)
Ø
3/
4
”
3/
4
”
1”
1”
1
1/
2
”
1
1/
2
”
Primary connection (female BSP)
Ø
1"
1"
1"
1"
1"
1"
Dimensions A
mm
1432
1953
1784
1784
2134
2134
B
mm
620
620
720
720
720
720
C
mm
720
720
800
800
800
800
D
mm
1282
1800
1627
1627
1985
1985
E
mm
290
290
300
300
300
300
Weight empty
Kg
115
155
202
202
230
230
Weight full
Kg
276
397
497
497
524
524
E-Tech S
E-Tech S
E-Tech S
E-Tech S
E-Tech S
E-Tech S
160
240
290
290
380
380
Single Phase Single Phase
Single Phase
Tri-Phase
Single Phase
Tri-Phase
Peak flow 40°C
L/10'
310
532
645
660
855
870
Peak flow 45°C
L/10'
250
452
548
561
725
739
Peak flow 60°C
L/10'
168
294
356
365
468
472
Peak flow 40°C
L/60'
690
880
990
1305
1200
1516
Peak flow 45°C
L/60'
570
750
845
1090
1021
1270
Peak flow 60°C
L/60'
375
465
527
625
636
752
Continuous flow 40°C
L/h
413
413
413
826
413
826
Continuous flow 45°C
L/h
354
354
354
708
354
708
Continuous flow 60°C
L/h
248
248
248
415
248
448
Heat up time to 80°C
min
61
93
113
91
150
120
E-T
ech S