Technical Specifications
HM60
HM60
Oil
Gas/LPG
Code
04124101
04124101
Fuel
Oil (28 sec or 35 sec)
Natural gas/LPG
Burner options
type
Riello
BG2000-S or Riello
Input
kW
69.9
69.9
Maximum output
kW
62.5
63.0
Primary capacity
L
82
82
Total capacity
L
162
162
Heating surface area
m
2
2.46
2.46
Primary circuit pressure drop
mbar
54
54
DHW tank pressure drop
mbar
45
45
Flue circuit pressure drop
mbar
0.6
0.6
DHW connection (male BSP)
Ø
3/
4
”
3/
4
”
Primary connection (female BSP)
Ø
1
1/
2
”
1
1/
2
”
Flue connection (G)
Ø mm
150
150
Flue connection options
type
B23
B23/C13/C33/C53
Dimensions
A
mm
1698
1698
B
mm
1583
1583
C
mm
538
538
D
mm
791
801(BG 2000)/838(Riello)
E
mm
540
540
F
mm
390
390
H
mm
1098
1098
J
mm
281
281
BG2000 air intake connection
Ø mm
n/a
80
Weight empty
Kg
229
229
Weight full
Kg
391
391
Minimum working gas pressure
mbar
n/a
20(Nat Gas)/37(LPG)
Gas flow rate
m
3
/h
n/a
7.40(Nat Gas/2.86(LPG)
HM60
Peak flow 40°C
L/10'
474
Peak flow 45°C
L/10'
378
Peak flow 60°C
L/10'
245
Peak flow 40°C
L/60'
1942
Peak flow 45°C
L/60'
1656
Peak flow 60°C
L/60'
1106
Continuous flow 40°C
L/h
1835
Continuous flow 45°C
L/h
1573
Continuous flow 60°C
L/h
1101
Reheat time to 60°C
min
9
(all burners)
Maximum Operating Pressure
Primary:
3 bar
Secondary:
10 bar
Factory Test Pressure
Primary:
4.5 bar
Secondary:
13 bar
Maximum Operating Temperature
90°C
Power Supply
230v 50Hz
Domestic Hot Water Performances
Note : These performances are based on the hot water being
blended at point of use, with a boiler temperature of
90
°C
and a domestic cold water inlet of 10
°C.
Hea