6
Right Hand Side
Top
Front
Maximum Operating Pressure
Primary:
5 bar
Secondary:
10 bar
Factory Test Pressure
Primary:
7.5 bar
Secondary:
13 bar
Maximum Operating Temperature
90°C
HR 601
Code
06204401
Total capacity
L
606
Primary capacity
L
161
Heating surface area
m
2
3.58
Primary pressure drop
mbar
92
Primary flow rate
L/h
7200
Max. absorbed boiler output
kW
88
Primary connections (female BSP)
Ø
2"
Hot water connections (male BSP)
Ø
1
1/
2
"
Weight empty
Kg
240
Weight full
Kg
846
Wrexham Maelor Hospital, North Wales
Four HR601's installed in battery formation providing 2824 litres of hot water at 60°C in 10 minutes and a continuous
output of 4928 litres per hour for the new extension to this general hospital in North Wales.
Technical Specifications
HR 601
Peak flow 40°C
L/10’
1345
Peak flow 45°C
L/10’
1153
Peak flow 60°C
L/10’
706
Peak flow 1st hour 40°C
L/60’
3437
Peak flow 1st hour 45°C
L/60’
2946
Peak flow 1st hour 60°C
L/60’
1733
Continuous flow 40°C
L/h
2511
Continuous flow 45°C
L/h
2152
Continuous flow 60°C
L/h
1232
HR 601
Note: The above performances are based on a primary flow temperature of 85°C and a domestic cold water inlet of 10°C,
without the use of a thermostatic mixing valve on the domestic hot water outlet.
Project Reference
Domestic Hot Water Performances