44
42
Technical Specifications
Maximum Operating Pressure
Primary:
3 bar
Factory Test Pressure
Primary:
4.5 bar
Maximum Operating Temperature
90°C
Power Supply
230v 50Hz
Code
01130501
01130601
01130701
Fuel
Oil (28 sec or 35 sec) or Natural gas/LPG
Burner options
Riello oil - Riello pressure jet natural gas/LPG
Minimum input
kW
22
30
40
Maximum input
kW
28
41
57
Minimum output
kW
20
28
36.5
Maximum output
kW
25
36
51
Total capacity
L
31
37
53
Primary connection (female BSP)
Ø
1”
1”
1
1/
4
”
Flue circuit pressure drop
mbar
0.15
0.17
0.15
Flue connection (D)
mm
130
130
150
Dimensions
A
mm
470
470
530
B
mm
700
765
805
C
mm
566
566
656
E
mm
550
615
645
F mm
445
510
550
G
mm
260
260
260
Weight empty (excluding burner)
Kg
108
122
157
Weight full (excluding burner)
Kg
139
159
210
Compact N1
Compact N2
Compact N3
Simple Installation
The Compact N is supplied fully assembled, with its
robust casing and insulation fitted in the factory.
This makes for a simple installation by the installer,
with heating flow and return and chimney
connections all easily accessible at the rear of the
boiler. There’s even a multi pin plug and socket for
electrical connection.
Co
m
p
a
ct
N