Technical Specifications
Maximum Operating Pressure
Primary:
5 bar
Factory Test Pressure
Primary:
7.5 bar
Maximum Operating Temperature
90°C
Code
04120101
04120201
04120301
Fuel
Oil (28 sec or 35 sec) or Natural gas/LPG
Burner options
Riello oil - Riello pressure jet natural gas/LPG
Minimum input
kW
82
134
197
Maximum input
kW
109
161
260
Minimum output
kW
74
115
185
Maximum output
kW
100
140
235
Mass rate of combustion products - gas
Kg/h
189
254
451
Mass rate of combustion products – oil
Kg/h
199
288
466
Total capacity
L
102
122
150
Primary connections (flange)
Ø
DN50
DN50
DN65
Safety valve connection (female BSP)
Ø
1”
1”
1”
Open vent connection (female BSP)
Ø
1”
1”
1”
Primary pressure drop
mbar
2 - 5
5 - 11
11 - 31
Flue circuit pressure drop
mbar
0.22 – 0.48
0.68 – 0.96
1.83 – 2.5
Flue connection
mm
200
200
200
Dimensions (excluding burner)
Length
mm
1295
1495
1795
Height
mm
1000
1000
1000
Width
mm
796
796
796
Weight empty (excluding burner)
Kg
315
380
470
Weight full (excluding burner)
Kg
417
502
620
CA100
CA150
CA200
Control Panel
The control panel includes :
- On/off switch
- Thermometer
- High/Low thermostats
- High/Low indicator lamps
- High limit thermostat
- Door open warning lamp
Birley Secondary School, Sheffield
A temporary plantroom housed three CA200
boilers providing 705kW of heating for the
temporary teaching classrooms whilst the
school was rebuilt. The boilers were then
moved into their permanent home in a new
plantroom once the building was completed.
C
o
mpac
t A
Project Reference