42
Error Code
Controller Stoppage Code
Code
Symptoms
Code
Symptoms
00-14
0#...14# communication failure of slave units
44
Main pipe outlet water temperature sensor malfunctioned
16
Compressor no.1 of system no.1 overloaded
Compressor no.1 of system no.2 overloaded
45
Inlet water temperature sensor failed
17
46
Outlet water temperature sensor failed
18
Water pump overload
47
Ambient temperature sensor failed
19
fl
ow rate failure
48
System 1 heat exchanger outlet temperature sensor failed
20
System 1 high pressure
49
System 2 heat exchanger outlet temperature sensor failed
21
System 1 low pressure
50
System 1 suction temperature sensor failed
24
System 2 high pressure
51
System 2 suction temperature sensor failed
25
Anti-freezing protection failure
52
System 2 low pressure sensor failed
26
Electric heater for water system overloaded
53
System 1 low pressure sensor failed
27
Ambient temperature too high/low
54
Memory failure
29
Suction superheat for system 1 too low
60
No system to startup
31
Communication failure between master and slave units
63
System 1 fan motor overloaded
32
Suction temperature for system 1 too high
64
System 2 fan motor overloaded
33
Discharge temperature for system 1 is too high
65
Temperature difference between
water inlet and outlet is too large
34
Suction temperature for system 2 is too high
66
Reverse connection of the water inlet temperature sensor
and water outlet temperature sensor
35
Discharge temperature of system 2 is too high
67
Master unit inlet water temperature sensor failed
36
System 2 low pressure
68
Compressor no.2 of system no.1 overloaded
37
Suction superheat for system 2 is too low
69
Compressor no.2 of system no.2 overloaded
38
System 1 leaking refrigerant
70
System 1 discharge temperature is abnormal
39
System 2 leaking refrigerant
71
System 2 discharge temperature is abnormal
40
System 1 discharge temperature sensor malfunctioned
78
Communication failure for all slave units
41
System 2 discharge temperature sensor malfunctioned
F6
Communication failure between wired controller and
master unit
42
System 1 middle heat exchanger
sensor malfunctioned
ERRO
DIP setting error
43
System 2 middle heat exchanger
sensor malfunctioned
Codes Displayed by the LED Indicator and Explanations
Code
Symptoms
Code
Symptoms
ECXX-14
Slave unit 0# ~ 14# communication failure
ER43
System 2 middle heat exchanger sensor malfunctioned
ER16
Compressor no.1 of system no.1 overloaded
ER44
Main pipe outlet water temperature sensor malfunctioned
ER17
Compressor no.1 of system no.2 overloaded
ER45
Inlet water temperature sensor failed
ER18
Water pump overloaded
ER46
Outlet water temperature sensor failed
ER19
fl
ow rate failure
ER47
Ambient temperature sensor failed
ER20
System 1 high pressure
ER48
System 1 heat exchanger outlet temperature sensor failed
ER21
System 1 low pressure
ER49
System 2 heat exchanger outlet temperature sensor failed
Summary of Contents for A5MAC 210D
Page 1: ...Technical Manual AIR COOLED MODULAR CHILLER A5MAC 210D A5MAC 230D A5MAC 340D A5MAC 450D...
Page 14: ...14 Wiring Diagrams MODEL A5MAC210 230D...
Page 15: ...16 1 4 5 3 2 7 8 6 1 4 5 3 2 7 8 6 A5MAC340DR...
Page 16: ...17 1 4 5 3 2 7 8 6 1 4 5 3 2 7 8 6 A5MAC450D...
Page 36: ...38 Wired Controller Instruction Dimensions Controller Installation...