13
Water Pressure Drop Curve
A5MAC210/230D
A5MAC340/450D(R)
NOTES:
1) THE WATER PRESSURE DROP OF THE UNIT IS THE TEST RESULT WHEN A PLATE HEAT EXCHANGER AND THE ACCESSORY
Y-SHAPED FILTER ARE INSTALLED.
2) THE WATER RESISTANCE OF THE PLATE HEAT EXCHANGER AND THE Y-SHAPED FILTER ARE TESTED WITH PURE WATER.IF
THE ONSITE WATER QUALITY CHANGES, THE TEST RESULT MAY BE DIFFERENT FROM THAT SHOWN IN THE FIGURE.
Sound Data
0
10
20
30
40
50
60
70
80
90
7
7.5
8
8.5
9
9.5
10
10.5
11
11.5
12
12.5
13
13.5
14
14.5
15
15.5
16
W
at
er
p
ress
ure
d
ro
p
(kP
a)
Water flow (m³/h)
Water pressure drop
A5MAC210D
A5MAC230D
A5MAC450D
A5MAC340DR
Test condition: Octave band level noise is tested base on 11.5dB(A) background noise semi-anechoic room.
Acoustic Noise
Units
Octave Band Level (dB,ref20
μ
Pa)
dB(A)
63Hz
125Hz
250Hz
500Hz
1kHz
2kHz
4kHz
8kHz
Overall
A5MAC210D
44.9
51.1
56.1
58.7
57.2
55.2
51.5
41.7
63.7
A5MAC230D
45.3
52.6
56
60.6
60.8
58.7
50.2
41.2
65.8
A5MAC340DR
53.4
53.5
59.1
60.0
62.8
58.1
52.6
45.2
67
A5MAC450D
54.3
55.0
60.4
61.2
65.4
60.8
54.0
46.7
69
Summary of Contents for A5MAC 210D
Page 1: ...Technical Manual AIR COOLED MODULAR CHILLER A5MAC 210D A5MAC 230D A5MAC 340D A5MAC 450D...
Page 14: ...14 Wiring Diagrams MODEL A5MAC210 230D...
Page 15: ...16 1 4 5 3 2 7 8 6 1 4 5 3 2 7 8 6 A5MAC340DR...
Page 16: ...17 1 4 5 3 2 7 8 6 1 4 5 3 2 7 8 6 A5MAC450D...
Page 36: ...38 Wired Controller Instruction Dimensions Controller Installation...