33
Maintenance
The unit need to be checked on a routine basis to maintain optimum performance and minimize breakdown
maintenance. The following needs to be checked on a routine basis:
Items
Monthly
Quarterly
Once half a
year
Once a year
If necessary
1. Compressor
Performance appraisal; whether there is
abnormal sound
●
Whether wires are securely connected
●
Whether the working current is abnormal
(
fl
uctuation: 10%)
▲
Discharge air temperature of the compressor
▲
Check the oil level
▲
Check the color of the lubricant
▲
2. Controller
Check parameter settings
▲
Check protective device
▲
Delay protector
▲
Phase order protector
▲
High/low pressure switch
▲
Differential water pressure switch/water
fl
ow
switch
▲
Overload protector
▲
Protector against extreme temperature of
discharged air
▲
3. Plate heat exchanger
Check the water quality
●
Clean the plate heat exchanger
▲
Seasonal protection measures
▲
(anti-freeze in winter)
4. Fin heat exchanger
▲
5. Others
or replaced
●
Whether bolts have loosened
●
NOTE:
THE PRECEDING MAINTENANCE PLAN IS FOR REFERENCE ONLY. THE MAINTENANCE PLAN MAY VARY BASED ON REGION.
●
INDICATES ITEMS TO BE CHECKED BY CUSTOMERS;
▲
INDICATES ITEMS TO BE CHECKED BY SERVICE PERSONNEL.