ACS-CONTROL-SYSTEM GmbH
l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
17
Switch Delay Time / Reset Switch Delay Time
– extended menu structure
The activation resp. deactivation of the switch output can be biased with a delay time (resolution
0,01s), to realize simple sequence control system.
The input range is indefinite.
Default > 0s
Function
– extended menu structure
Hysteresis function
The hysteresis function realizes a stable switch state, independent from system conditioned signal
fluctuations around the adjusted set point.
It can be used for realizing a signal controlled two-position control.
The switch range is determined by definition of switch point and reset switch point.
The switch output is activated, if the current measuring value exceeds the switch point and if the set
switch point delay time has been expired.
The switch output is deactivated, if the current measuring value exceeds the reset switch point and if
the set reset switch point delay time has been expired.
At inverse measuring principle, e.g. distance measurement, the switch output is activated, if the
current measuring value underrun the switch point and if the set switch point delay time has been
expired.
Accordingly the switch output is deactivated, if the current measuring value exceeds the reset switch
point and if the set reset switch point delay time has been expired.
Window function
The window function realizes a signal range – acceptance region –, where the switch output is set to a
definitive switch state.
The switch range is determined by definition of switch point and reset switch point.
The switch output is activated, if the current measuring value is inside the area that is defined by the
switch point and the reset switch point and if the set switch point delay time has been expired.
The switch output is deactivated, if the current measuring value is outside the area that is defined
by the switch point and the reset switch point and if the set reset switch point delay time has been
expired.
Summary of Contents for Sonicont USN020
Page 45: ......