ACS-CONTROL-SYSTEM GmbH
l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
36
Start-up procedure
Level measurement
The filling level is calculated by the device due to the distance of the filling material surface to the
sensor.
Sub menu Basic Setting
•
Commissioning
•
Min/Max Adjustment
Sub menu Display
•
Indicator value fill level
Example
Measurement task
•
Distance Sensor - container bottom:1,8m
•
Minimum filling level: 0m >> distance 1,8m – 0m = 1,8m
•
Maximum filling level:1,4m >> distance 1,8m – 1,4m = 0,4m
Settings
•
Process commissioning
•
Min/Max Adjustment: 1,8m = 0% / 0,4m = 100%
A - Filling level
B - Distance sensor – filling material surface
C - Distance sensor – container bottom
Summary of Contents for Sonicont USN020