Volume measurement
For the indication of the tank volume a display scaling can be made.
If a nonlinear tank style is used, a linearization must be set.
Predefined linearization curves for some tank styles are available.
Sub menu Basic Setting
•
Commissioning
•
Min/Max Adjustment
•
Linearization
Sub menu Display
•
Indicator value Scaled
•
Unit
•
Scaling - ration percent / tank volume
Example
Measurement task
•
Distance Sensor - container bottom:1,8m
•
Container: Cylinder - linear volume
•
Minimum filling level: 0,2m >> distance 1,8m – 0,2m = 1,6m
•
Maximum filling level: 1,2m >> distance 1,8m – 1,2m = 0,6m
•
Minimum volume: 0 liter
•
Maximum volume: 2000 liter
Settings
•
Process commissioning
•
Min/Max Adjustment: 1,6m = 0% / 0,6m = 100%
•
Linearization: Linear
•
Display Indicator value: Scaled
•
Display Unit: l
•
Display Scaling: 0% = 0 l / 100% = 2000l
A - Minimum volume
B - Distance at minimum volume
C - Maximum volume
D - Distance at maximum volume
E - Distance sensor - container bottom