41
3.2.15.
TSP parameters that can be set from the interface and from Remote Control
Parameter
Settable values
Default values
Note
P01
Boiler type selection
0 ÷ 8
0: PLAY
1: PLAY SV
0 = instantaneous
1 = with boiler thermostat
2 = with cylinder temperature probe
3 = heating only
P02
Gas type selection
0 - 1
0
1.
0 =
natural gas
1 = GPL
P03
DHW control type selection
0 - 1
1
0 =
flow switch
1 =
flowmeter
P04
Regulation coefficient with external probe
0 ÷ 90
30
P05
Anti Fast Cycles time
0 ÷ 10 min
3
P06
1
DO NOT MODIFY
P07
Ignition Heating ramp [value 1=10s]
0 ÷ 80
12
P08
Maximum heating power selection
(PREMIX)
P10...100
75%
P09
DHW maximum power selection
P10…100
100%
P10
Minimum power selection
0…P09
0%
P11
Minimum setpoint value selection
heating
20...P12
25°C
P12
Selection of the maximum value of the setpoint
heating
P11…80
80°C
P13
DHW setpoint maximum value selection
35 ÷ 67
60°C
P14
Calibration type selection
0 ÷ 20
0
0 = manu
5 = auto
P15
Boiler power selection
0 ÷ 4
0
0 = 24 kW
1 = 28 kW
2 = 32 kW
3 = 16 kW
4 = non usato
P16
Not used
P17
Not used
P18
Not used
P19
Thermostat (0) / Smoke probe (1)
0 - 1
1
DO NOT MODIFY
P20
DHW setpoint minimum value selection
35 ÷ 50
35
P21
Selection of low temperature zones
0 - 1
0
0 =
high temperature
1 =
low temperature
P22
Not used
P23
Pump activation time selection
(min): cold zone
0 ÷ 10
0
P24
Child protection
0 ÷ 1
0
1 =
active protection
P25
Not used
P26
Water hammer delay selection (sec)
0 ÷ 3
0
P27
Preheating OFF temperature selection (°C)
30 ÷ 75
45
P30
Not used
P31
Fan switch-on speed selection)
(P31 x 25) rpm
80 ÷ 160
140
P32
Maximum fan speed selection
(P32 x 25) + 2000) rpm
P33...255
170
P33
Minimum fan speed selection (P33 x 25)
30 ÷ 60
36
P36
Not used
P37
Probe AUX configuration
3 ÷ 3
3
DO NOT MODIFY
P38
Antifreeze temperature selection
0…+10
5
P39
Heating post-circulation time selection
0 ÷ 99 sec x 10
120
P40
Switch-on delay time selection
heating
0 ÷ 60 sec x 5
0
P41
DHW modulation selection with flowmeter
0 ÷ 1
1
0 =
not active
1 =
active
1.
P42
Select enable / disable DHW
pre-heating function
0 ÷ 1
0
0 =
disabled
1 =
enabled
P43
Selection of DHW activation delay time
with solar configuration
0 ÷ 30 sec
0
P44
Pressure sensor type selection
0 - 1
1
0 =
pressure switch
1 =
transducer
P45
Anti-legionella function selection (boiler only)
54, 55 ÷ 80
54
54 =
disabled
55 ÷ 80 =
delivery temperature set