BUFFER VPD SETTING
The buffer figure will create a trigger-off point below your set trigger point to prevent your device
from shutting off too quickly. Press the up or down button to cycle through buffer range from 0.1
kPa and 1.0 kPa.
In high VPD triggers, your device will turn on, only turning off when the VPD falls below your
buffer setting.
In low VPD triggers, your device will turn on, only turning off when the VPD rises above your set
buffer setting.
EXAMPLE
For example, if you had set a High VPD Trigger at 2.51 kPa and set a VPD Buffer at 0.2 kPa.
Then your device will trigger on when it meets or rises above 2.51 kPa, and only trigger off when
it falls below 2.31 kPa%. The 2.51 kPa figure is obtained by taking your High VPD Trigger of
2.51% and subtracting your VPD Buffer of 0.2 kPa.
PROGRAMMING
CONTROLLER 69 PRO
BUFF.
2.51
kPa
2.31
kPa
0.2
kPa
This setting will only appear in ports connected with outlet adapters.