p-40-ed-2-en
9.1
04-03-08
9
Error Codes (Malfunction Diagnostics)
The control system of the drive cyclically tests its own functional condition and the functional condition
of the complete drive system.
Malfunctions are signalled via the display of the external control panel, for instance:
Summary of the malfunctions:
Malfunction-No.
Reason
Remedy
11111
Treadle not in zero position
Bring treadle in zero position, check the
when mains power is
treadle, connect the Speed control unit.
turned ON.
9
9
9
9
9
Start lock is active.
Eliminate cause.
10
10
10
10
10
Machine class (<799>) was
Turn mains power switch OFF and ON again.
changed.
62
62
62
62
62
Short circuit on 24 V (32 V) DC.
Find short circuit and eliminate it
Turn mains power switch OFF and ON again.
63
63
63
63
63
Overload on 24 V (32 V) DC,
Turn mains power switch OFF and ON again
load current > 4 amps.
search component (magnet), what was the
reason why. Adjust new the magnet or
change it.
64
64
64
64
64
voltage too low (90 V - 150 V)
let check the voltage from a specialist.
( U < 150V ).
65
65
65
65
65
Power electronics not operational
Turn mains power switch OFF and ON again,
after mains power ON,
if the malfunction still happens, then change
mains power < 130V.
the control box.
66
66
66
66
66
Earth short (motor or motor supply line
Change the control box or the motor.
has earth short in one or more phases).
67
67
67
67
67
Internal malfunction
Change the control box.
E
ERROR
1