95
1
O PER AT I O N , M A I N T EN A N C E , A N D I N S TA L L AT I O N G U I D E
—
6.2 Warnings
LCD
Touch
Message (continued)
Fault
Action
Local bus
Communication between HMI and
switch controller is off
Check connection
Ethernet
disconnected
Ethernet module not connected
Check connection
Fire Fighting
Fire fighting input activated
Alarm is active and disables transfer
operations as long as the input is active
Control Voltage
Failure
Control voltage dropped during switch
control
Check power source
Control Voltage Low
Switch control voltage is below the
minimum
Check power source
Configuration Error
Invalid configuration
Check parameter values
IEC 61850 Error
IEC 61850 failure
Check configuration file
Ekip Com Hub Alarm
Ekip Com Hub failure
Check configuration
HMI Not Compatible
Firmware versions of HMI and device
are not compatible to be used together
Check current versions and update
compatible versions
Table 6.1 Alarms-list in level 3 and 4, LCD and touch control interfaces
Message
Reason
S1 and S2 not in sync
Voltage sources are not synchronized
Voltage Not Calibrated
Calibration data in power module is invalid or unavailable
Current Not Calibrated
Calibration data in current measurement module is invalid or unavailable
Pole temperature warning
Measured pole temperature is near the alarm level
Control Retry
Failed transfer sequence retry activated
Auto Control Disabled
Device is in manual operating mode
Local Bus
Module heartbeat error.
Check connection. Can be cleared using "Alarm Reset".
Configuration
Configuration session ports are open
Clock capacitor charging
Real time clock is not yet operational, date & time setting is disabled as
long as this warning is active. Clock capacitor is charged from source
voltage (not AUX) and takes about 10 minutes
—
Table 6.2 Warnings-list in level 3 and 4, LCD and touch control interfaces
Summary of Contents for Zenith ZTS T Series
Page 2: ...2 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 6: ...6 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 10: ...10 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 36: ...36 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 44: ...44 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 106: ...106 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 108: ...108 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 122: ...2 122 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 126: ...2 126 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 129: ...129 1 OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...