Z E N ITH Z T S ( D) T-S E R I E S 16 0 0 -3 0 0 0 A & Z T S C T T-S E R I E S 10 0 -3 0 0 0 A
Automatic transfer switch, I/O contacts
Cabling
Rating / Remark
Generator start/stop Cable size:
".08…1.5 mm²
28…16 AWG"
Stripping length; 6,5 mm, 0,255"
Generator 1 start/stop NC
T8 - 1
Common 1, voltage supply
T8 - 2 5 A@250 Vac (AC-1), 5 A@30 Vdc
Generator 1 start/stop NO
T8 - 3
Generator 2 start/stop NC
T8 - 4
Common 2, voltage supply
T8 - 5 5 A@250 Vac (AC-1), 5 A@30 Vdc
Generator 2 start/stop NO
T8 - 6
Output relay features Cable size:
".08…1.5 mm²
28…16 AWG"
Common, voltage supply 1
T7 - 1 5 A@250 Vac (AC-1), 5 A@30 Vdc
Programmable output 1
T7 - 2
Common, voltage supply 2
T7 - 3 5 A@250 Vac (AC-1), 5 A@30 Vdc
Programmable output 2
T7 - 4
Common, voltage supply 3
T7 - 5 5 A@250 Vac (AC-1), 5 A@30 Vdc
Programmable output 3
T7 - 6
Common, voltage supply 4
T7 - 7 5 A@250 Vac (AC-1), 5 A@30 Vdc
Programmable output 4
T7 - 8
¹
Refer to programming/I/O packages for terminal usage
Fire Fighting applications Cable size:
".08…1.5 mm²
28…16 AWG"
Only in ZTSD/CT-types, delayed/
closed transition, I-O-II or II-O-I
Fire fighting input 24 Vdc (+)
T9 - 1
Fire fighting input 24 Vdc (-)
T9 - 2
Input contact features Cable size:
".08…1.5 mm²
28…16 AWG"
"Do not connect to any
power supply"
Common input
T9 - 3
24 Vdc 5 mA
Level 4
Level 4 = HMI with touch screen
Programmable input 1
(default, Emergency stop)
T9 - 4
Programmable input 2
(default, Remote test on
load)
T9 - 5
Programmable input 3
(default, Remote test off
load)
T9 - 6 Only in ZTSD/CT-types, delayed/
closed transition, I-O-II or II-O-I
¹
Refer to programming/I/O packages for terminal usage
—
Table 7.1 Automatic transfer switch I/O contacts
Summary of Contents for Zenith ZTS T Series
Page 2: ...2 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 6: ...6 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 10: ...10 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 36: ...36 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 44: ...44 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 106: ...106 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 108: ...108 1 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 122: ...2 122 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 126: ...2 126 ZENITH ZTS D T SERIES 1600 3000 A ZTSCT T SERIES 100 3000 A ...
Page 129: ...129 1 OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...